Data Sheet
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
2 / 2
Modbus
BACnet
RTU
TCP
MSTP
IP
Connection
EIA485 (3 wire isolated)
EIA232 (DB9 connector)
10BASE-T
100BASE-TX
EIA485
(3 wire isolated)
10BASE-T
100BASE-TX
Date rate
2.4, 4.8, 9.6, 19.2, 38.4,
57.6, 115.2 kbps
10 Mbps
100 Mbps
9.6, 19.2, 38.4,
57.6, 76.8, 115.2 kbps
10 Mbps
100 Mbps
Data Types
&
Functions
supported
1-Read Digital Outputs
2-Read Digital Inputs
3-Read Holding Registers
4-Read Analog Registers
5-Write Single Digital Output
6-Write Single Analog Register
15-Write Multiple Digital Output
16-Write Multiple Holding Registers
0-AO (Analog Output)
1-AI (Analog Input)
2-AV (Analog Value)
3-BO (Binary Output)
4-BI (Binary Input)
5-BV (Binary Value)
12-LOOP
13-MI (Multistate Input)
14-MO (Multistate Output)
15-MV (Multistate Value)
23-ACUM (Accumulator)
Enclosure
Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh): 90x88x56 mm
Recommended space for installation (dxwxh): 130x100x100mm
Color: Light Grey. RAL 7035
Battery
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Mounting
Wall.
DIN rail EN60715 TH35.
Console
Port
Mini Type-B USB 2.0 compliant
1500VDC isolation
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
If cables are more than 3.05 meters long, Class 2 cable is required.
USB port
Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150mA
(HDD connection not allowed)
Power
1 x Plug-in screw terminal block (3 poles)
9 to 36VDC +/-10%, Max.: 140mA.
24VAC +/-10% 50-60Hz, Max.: 127mA
Recommended: 24VDC
Push Button
Button A: Will broadcast I-Am message in the
BACnet network
Button B: Reserved for future use
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Operation
Temperature
0°C to +60°C
Port A
1 x Serial EIA485 Plug-in screw orange terminal block (2 poles)
A, B
1 x Plug-in screw terminal block green (2 poles)
SGND (Reference ground or shield)
1500VDC isolation from other ports
Operational
Humidity
5 to 95%, no condensation
Protection
IP20 (IEC60529)
Switch A
(SWA)
1 x DIP-Switch for PORT A configuration:
Position 1:
ON: 120 Ω termination active
Off: 120 Ω termination inactive (default)
Position 2-3:
ON: Polarization active (default)
Off: Polarization inactive
LED
Indicators
10 x Onboard LED indicators
2 x Run (Power)/Error
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
PORT B
1 x Serial EIA232 (SUB-D9 male connector)
Pinout from a DTE device
1500VDC isolation from other ports
(except PORT B: EIA485)
1 x Serial EIA485 Plug-in screw terminal block (3 poles)
A, B, SG (Reference ground or shield)
1500VDC isolation from other ports
(except PORT B: EIA232)
Switch B
(SWB)
1 x DIP-Switch for serial EIA485 configuration:
Position 1:
ON: 120 Ω termination active (default)
Off: 120 Ω termination inactive
Position 2-3:
ON: Polarization active
Off: Polarization inactive (default)
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply
BACnet
MSTP
Ethernet
Modbus TCP
BACnet IP
USB
storage
Modbus RTU
EIA485
Console
Port
Modbus RTU
EIA232
PROTOCOLS
BACnet is the Data Communication Protocol for
Building Automation and Control Networks.
Developed under the auspices of the American
Society of Heating, Refrigerating and Air-
Conditioning Engineers (ASHRAE).
BACnet is an American national standard, a
European standard, a national standard in more
than 30 countries, and an ISO global standard.
The protocol is supported and maintained by
ASHRAE Standing Standard Project Committee
135.
For further information, please visit
www.bacnet.org
Modbus Protocol is a de facto standard, truly
open and the most widely used network protocol
in the industrial manufacturing environment.
Modbus is used in multiple applications to
monitor and program devices; to communicate
between intelligent devices and sensors and
instruments; to monitor field devices using PCs
and HMIs.
But Modbus is not only an industrial protocol.
Building, infrastructure, transportation and
energy applications also make use of its
benefits.
For further information visit www.modbus.org
COMMUNICATION
100 mm (h)
100 mm
(w)
130 mm
(d)