User's Manual
3.1.3 Wiring the AUX
Relay for Use as
Propped Door
The Propped Door Relay output function informs per-
sonnel that the door is being held open, or “propped”
open, after a valid entry. By default, the Propped Door
output is assigned to audio alert #2. To use the Aux
Relay, you must first assign it. See command below.
The Aux relay is rated to handle two amps of current
at 12 VDC, and turns ON or OFF one leg of the power
to a warning device. (Warning device not included
with the IEI unit.) To incorporate this feature, follow
thestepsbelow;seeFigure3-3.
3.1.3.A Wiring the Propped Door Relay
1. Turn OFF power to the prox.pad plus unit, and
then unlatch the keypad from the plastic housing.
2. Locate connector P2 (the 6-pin connector) on the
main circuit board.
3. Connect the 6-conductor harness to connector P2.
(The 2-pin jumper o n pins 5 and 6 of connector
P2 must be removed first.)
4. Connect the green wire (NO) to V+ on the
sounder.
5. Connectthebluewire(C)toV+onthepower
supply.
6. Connect V- from the power supply to V- on the
sounder. The gray wire is not used.
NOTE: To use the default 30-second Propped Door
Relay time, no programm ing is necessary. To
change this default (from 30 to 990 seconds), use
command 44 # ttt # 0 ** after the unit is installed
successfully; for details, see section 4.3.3.
NOTE: PROGRAMMING FOR PROPPED DOOR:
To assign the Propped Door output to the Aux
Relay, enter the following on the key pad:
10#3#2#**
To disable audio alert #2, enter:
10#0#6#**
3.1 Wiring the prox.pad plus Unit Chapter 3: Wiring
prox.pad plus Install/Program. Manual, PPP, D2 3-5