User's Manual
A7817A
7
2.2 Operating the Solenoid
The Reader operates a solenoid locking device. Once the access control system
validates the users keypad or card data, the door can now be unlocked. Shorting the
two lock terminals on the Interface Module together activates the locking device.
Connect these terminals to a normally open dry contact on the access control panel
used to control the door. When the short is removed the locking device returns to the
locked condition. The solenoid configuration is discussed in section 3.2.
2.3 Controlling the Request to Exit, Door Position Switch,
Deadbolt Monitor and Latch Bolt Monitor
The Reader is equipped with a Request to Exit (RX) input, a Door Position Switch
(DPS) input, a Deadbolt (DX) Monitor and a Latch Bolt (LX) Monitor. These are located
on connector J3. On this connector there is a Loop Common connection (pin 1). To
operate these inputs just short the desired input to the Loop Common wire. When the
RX or DSP inputs are closed, the corresponding relay on the Interface Module is
energized. When the LX input is closed the Aux 1 relay on the Aux Relay Board is
energized and when the DX is closed the Aux 2 relay is energized. See section 4.8 for
further details.