User Manual
To communicate with the LS2/LS2P system, commu-
nications must first be unlocked either by entering a
Comm. Enable code (user type 8), the master code, or
supervisor code.
1.3.13 DoorGard
LS2/LS2P Default
Settings
Table 1-2 lists the default settings for the DoorGard
LS2/LS2P system as shipped from the factory. Sub-
sequent sections in this chapter explain how to change
these default settings or program additional functions.
Table 1-2. DoorGard LS2/LS2P Default Settings
Parameter Default Setting Cross-Reference
Master Code
(user location 1)
1234 See section 1.2.1
Main Relay energizes for Five (5) seconds See section 1.3.1
Audible Keypress
Feedback
ON See section 1.3.7
Visual Keypress Feedback ON See section 1.3.8
Auto Entry
(no * required)
DISABLED See section 1.3.9
Error Lockout
ENABLED
(cannot be disabled)
See section 1.3.6
Error Lockout Duration 10 seconds
See Table 1-5, command
32, parameter 1
Error Lockout Threshold 3 attempts
See Table 1-5, command
32, parameter 0
User Lockout Codes ENABLED See section 1.3.5
Forced Door Alert DISABLED See sections 1.3.2-1.3.3
Propped Door Alert DISABLED See sections 1.3.2-1.3.3
Event Logging All ENABLED
See Table 1-5, command
73
1.3 Programming Keypad Options and Parameters
1-16 DoorGard LS2/LS2P System Programming Manual, D3