Our durable lineup of die-cast, low-profile and plastic weatherproof
covers offers rugged protection in all types of applications, including
industrial, commercial, residential and more! Time-saving features,
premium construction and an array of customization options make
them a welcome addition to any project.
STAY COMPLIANT 2017 NEC Code, Article 406.9 (B)(1)
Intermatic Weatherproof Covers meet or exceed the latest NEC requirements for extra-duty applications and wet locations.
For the 2017 NEC, all 15 and 20 ampere, 125 and 250 volt receptacles installed in a wet location still must have an
enclosure and covers that are weatherproof whether an attachment plug cap is inserted or not.
A revision now requires all enclosures and covers installed in wet locations for 15 and 20 ampere, 125 and 250 volt
receptacles to be listed, and of the "extra-duty” type, not just boxes supported from grade.
This requirement is now also required for dwelling units as well. The requirement for weather-resistant type receptacles
in wet locations is still applicable in the 2017 NEC. This change also provoked changes to Article 590.4(D)(2) for extra-duty
covers for all 15 and 20 ampere, 125 and 250 volt receptacles installed at temporary installations in a wet location.
Exceeds the CEC Section 26-702.
Standard weatherproof cover compliance guidelines apply only to 2014 Article 314.15.