Specification

www.intermatic.com
Energy Controls
Diagrams
ST700 Series
Specification
The timer shall be a solid state electronic control, capable of permitting 42 event settings to be distributed through a
7-Day time period, plus one Astro ON and one Astro OFF setpoint per day. The time-of-day event settings shall be
programmable to the nearest minute with a minimum ON duration of 1 minute and a maximum ON duration of 6 days,
23 hours, 59 minutes. The timer shall have a digital LCD to show mode, current on/off status, day and time and next
event (STW700W shows icons in upper right hand corner to depic current communication status). The timer shall provide
a manual override control for both temporary and permanent overrides. The timer shall operate over a temperature range
of 32°F to 104°F (0°C to 40°C). User program selections are stored in a non-volatile memory. Switch conguration to be
SPST with a UL listed rating of: General Purpose: 15 A, 120 VAC, 50/60 Hz; Tungsten: 8 A, 120 VAC, 50/60 Hz;
Inductive: 15 A, 120 VAC, 50/60 Hz; Electronic Ballast: 5 A, 120 VAC, 50/60 Hz; Motor: 1 HP, 120 VAC. The timer must t
in a standard wall box and accept a rectangular decorator wall plate. Timer contacts shall make or break current
according to user adjustable program. The timer shall be Intermatic model ____________________(ST700W)(STW700W).
Load
Power
Source
A
B
C
D
E
120 V
Line
Wire C
Wire B
Wire E
Wire A
Wire D
Neutral
Load
Timer
Load
Power
Source
A
B
C
D
E
Jumper
120 V
Line
Wire A
Wire D
Wire C
Wire E
Wire B
Neutral
Load
TimerSwitch
Single-Pole Wiring Three-Way Wiring
Blue — Connects to black wire from Load
White — Connects to white (neutral) wire from Load and Power
Source
Black — Connects to black (hot) wire from Power Source
Green — Connects to ground
Red — Not used in single-pole installations
A
B
C
D
E
Blue — Connects to black wire from Load
White — Connects to white (neutral) wire from Load and Power
Source
Black — Connects to black (hot) wire from Power Source
Green — Connects to ground
Red — Connects through remote switch to black (hot) wire from
Power Source
A
B
C
D
E
300TS10134