User Guide

WIRING DIAGRAMS
SILENCE NORMAL TEST
SILENCE NORMAL TEST
SILENCE NORMAL TEST
SILENCE NORMAL TEST
SILENCE NORMAL TEST
120/240 VAC Single Phase
120/208 VAC Three Phase Wye
277/480 VAC Three Phase Wye
480 VAC Three Phase Delta
120/240 VAC Three Phase High Leg Delta
L1
L2
L3
N
G
L1
L2
L3
N
G
L1
L2
L3
N
G
L1
L2
N
G
L1
L2
L3
G
BLACK
BLACK
BLACK
WHITE
GREEN
BLACK
BLACK
BLACK
WHITE
GREEN
BLACK
BLACK
BLACK
GREEN
BLACK
RED
BLACK
WHITE
GREEN
BLACK
BLACK
WHITE
GREEN
Figure 1
Figure 5
SILENCE NORMAL TEST
600 VAC Three Phase Delta
L1
L2
L3
G
BLACK
BLACK
BLACK
GREEN
Figure 7
Figure 3
Figure 4
SILENCE NORMAL TEST
347/600 VAC Three Phase Wye
L1
L2
L3
N
G
BLACK
BLACK
BLACK
WHITE
GREEN
Figure 6
Figure 2
NOTE: These wiring diagrams show installation of the PG
Series unit on the load side of a breaker. While these units have
internal fusing, it is recommended that a 60 to 100 amp breaker
be used as a disconnect. Refer to installation instruction number
4 on page 1.
MODELS:
PG3000-240-2S
PG3500-240-2S
MODELS:
PG3000-208-3Y
PG3500-208-3Y
M
ODELS:
PG3000-600-3Y
PG3500-600-3Y
MODELS:
PG3000-480-3Y
PG3500-480-3Y
MODELS
:
PG3000-480-3D
PG3500-480-3D
MODELS:
PG3000-600-3D
PG3500-600-3D
MODELS:
PG3000-240-3HLD
PG3500-240-3HLD
ALARM RELAY OUTPUT CONNECTIONS
1. Two Wire Closed Loop: Connect feed wire to the Common (C)
wire and return wire to the Normally Opened (N/O) wire. During
normal operation, the contact will be closed between C and N/O.
The contact will open during an alarm condition.
2. Two Wire Opened Loop: Connect the feed wire to the Common
( C ) wire and return wire to the Normally Closed (N/C) wire.
During normal operation, the contact will be opened between C
and N/C. The contact will close during an alarm condition.
3. Three Wire Supervised Loop: Connect feed wire to the
Common (C) wire, one return wire to the Normally Opened (N/O)
wire and the second return wire to the Normally Closed (N/C)
wire. During normal operation, the contact will be closed between
C and N/O and opened between C and N/C. An alarm condition
will reverse the condition.
4. Consult the instructions for your specific monitoring system for
additional information.
2
Brown - c
Brown - c
Violet - n/c
Orange - n/o
Orange - n/o
Violet - n/c
Normal operating condition - relay energized
Alarm condition - relay not
energized
SUGGESTED WIRE SIZES
SERIES UNDER 3’ UNDER 6’ OVER 6’
PG3000 10 AWG 8 AWG 6 AWG
PG3500 8 AWG 6 AWG 4 AWG