Installation Manual

TO SET FILTER TIME SWITCH, follow instructions on the right.
The length of the daily filtration/heating cycle depends on many vari-
ables such as size, shape, and geographic location of the pool, water
chemistry, type of pool equipment, usage and season of year. If not sure,
contact your local pool service professional for advice.
TO SET CLEANER TIME SWITCH, follow instructions on the right.
NOTE: This Control is factory wired to prevent equipment damage by
allowing the Cleaner Pump to operate only when the Filter Pump is
already operating. This requires that the Cleaner Time Switch settings
(ON and OFF times) must be within the operating hours of the Filter
Pump. For example: If the Filter Pump is set to operate from 8 am to 2
pm daily, the Cleaner Pump Time Switch should be set to operate no
longer than 8:30 am to 1:30 pm.
TO SET THERMOSTAT, turn dial, pointing to desired temperature,
marked on the plate, between 32˚F and 45˚F. Again, many variables
must be considered before selecting the “turn ON” temperature of the
Filter Pump and your local pool service professional is the best source
of information. The Thermostat is factory set to turn OFF the Filter Pump
when the ambient temperature rises 5˚F above its set point.
THE FIREMAN SWITCH (Heater Protection Mechanism), if installed, is
factory set and shuts OFF the heater 20 minutes before the Time Switch
turns OFF the filter pump. The Fireman Switch requires no setting or
service.
OPERATION
TIME SWITCH OPERATING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold TRIPPERS
against edge of CLOCK-DIAL, pointing to time (AM or
PM) when ON and OFF operations
are desired.Tighten tripper screws
firmly.
2. TO SET TIME-OF-DAY: Pull
CLOCK-DIAL outward. Turn in either
direction and align the exact time-of-
day on the CLOCK-DIAL (the time now, when switch is
being put into operation) to the POINTER.
DO NOT MOVE POINTER
• TO OPERATE SWITCH MANUALLY: Move
MANUAL LEVER below CLOCK-DIAL left or right as
indicated by arrows, This will not affect next
operation.
• FORMORETHANONEDAILYON-OFF
OPERATION: Place additional tripper pairs on CLOCK-
DIAL (order 156T1978A).
• INCASEOFPOWERFAILURE, reset CLOCK-DIAL
to proper time-of-day. See step 2 above.
CLOCK
DIAL
TIME
POINTER
OFF
TRIPPER
MANUAL
LEVER
ON
TRIPPER
TROUBLESHOOTING
SYMPTOM CAUSE(S) CORRECTIVE ACTION
1. Time Switch will not keep 1a. Frequent power outages Reset dial
time - dial is turning. 1b. Wrong voltage/cycle Change clock motor
1c. Loose clock motor connections Check connections
2. Time Switch Dial stops 2a. Loose tripper Check/change tripper
at ON or OFF tripper. 2b. Bent dial Check/change mechanism
2c. Defective motor Change clock motor
3. Load is ON at all times-- 3a. Welded contacts Change mechanism
dial is turning. 3b. Two ON-trippers on dial Change tripper
3c. No OFF tripper on dial Change tripper
3d. Defective mechanism Change mechanism
4. Dead clock motor. (Clock 4a. Defective clock motor (open Change clock motor
motor gears do not rotate.) coil due to lightning or surge)
4b. Loose clock motor connections Check connections
4c. Wrong voltage Change clock motor
5. Filter Pump will not start 5a. Defective thermostat Replace thermostat
when temp. is below 32˚F. 5b. Defective relay Replace relay
5c. Faulty wiring Check wiring
5d. Power outage Install stand-by power
3
WARNING: Do not disconnect high limit or pressure switches.
Figure 2