Cut Sheet

www.intermatic.com
Energy Controls
Diagrams
G8000 Series
Model VAC 60 Hz Switch Type Description
G8045-00 120 1 N.O./1 N.C. Time Initiated, Time Terminated
G8045-20 208-240 1 N.O./1 N.C. Time Initiated, Time Terminated
G8145-00 120 1 N.O./1 N.C. Time Initiated. Temperature, Pressure, or Time
Terminated.
G8145-20 208-240 1 N.O./1 N.C. Time Initiated. Temperature, Pressure, or Time
Terminated.
Specification
Furnish and install a Grässlin___________defrost control, which shall have up to 6 defrost cycles per day with initiation
times settable in 2 minute increments from 4-110 minutes. The defrost timer shall be housed in a UL Type 1 indoor me-
tallic enclosure or be supplied with suitable bracket mount. The contacts shall be 1N.O / 1N.C and rated for 40A Resis-
tive, 2 HP @ 240 VAC. Defrost termination to be by time (or by a remote temperature or pressure switch). Defrost time
switch shall comply with UL Refrigeration standard UL873.
7 ¾"
3"
5"
[12.70 cm]
[7.62 cm]
[19.69 cm]
Type 1 Steel
*For bracket mount (Comes in bulk packs of 20, No Enclosure) Add "B" to model number (i.e. G8045-00B)
G8045-00 G8045-20
G8145-00
G8145-20