Cut Sheet
www.intermatic.com
Surge Protectiion
Diagrams
AG Series
Specification
The Surge Protective Device shall be listed by CSA to ANSI/UL 1449 3rd Edition for SPD Type 1 and Type 2 locations. 
The Surge Protective Device shall provide protection between each phase conductor and ground. The Maximum  
Continuous Operating Voltage (MCOV) shall be a minimum of ____VAC between phase and ground. When subjected to 
the ANSI/UL 1449 3rd Edition testing impulses, the Voltage Protection Rating shall be no greater than ____ Volts Line to 
Neutral/Ground or ____Volts Line to Line. The Surge Protective device shall employ large MOV technology and provide 
individual component thermal protection and monitoring, utilizing a green LED status indicator light. The failure of a single 
component will turn the LED OFF. The rainproof housing shall be constructed of UV resistant polycarbonate, or material 
of equal strength and UV resistance, and tested to Type 4 standards for outdoor use. A 
1
⁄2 inch polycarbonate threaded 
nipple and metal locknut shall be provided. Leads shall be 12 gauge minimum and 24 inches in length. The Surge  
Protective Device shall carry a 1-year warranty and be manufactured by a company who has engaged in the manufacture 
of such products for a minimum of 5 years.
120/240 VAC Three wire with grounded 
neutral.
Found at Service entrances 
and Meter Cans.
Line
Line
Grounded/
Neutral
120 VAC
120 VAC
240 VAC 
WHITE
BLACK
BLACK
120/240 VAC Three wire with separate ground. 
Found in Main Disconnect Switches, 
Main Distribution panels, Load Centers 
Sub panels and equipment locations.
Line
Line
Neutral
Ground
120 
120 
240 VAC 
120 VAC 
BLACK
WHITE
120 VAC Two wire single phase with 
separate ground.
Found at connections for individual 
pieces of equipment such as pumps 
and single phase motors. NOTE: Both
black wires connect to Line. 
Line
Neutral
Ground
0 VAC 
120 VAC 
120 VAC 
WHITE
BLACK
BLACK
BLACK
VAC