User Guide

ERR 04 Clock time not setup
ERR 05 Clock date not setup
ERR 06 ASTRO not setup
ERR 07 HOLIDAY not setup
ERR 08 OVERRIDE not setup
ERR 09 ASTRO entry not applicable
ERR 10 COPY key not applicable
ERR 11 Unable to clear a set point in week long review mode –
set points may only be cleared from an individual
day’s program
ERR 12 Internal calculation error – may not be recoverable –
reset the time switch
ERR 13 Day groups may not be copied to or from
ERR 14 No ON or OFF time entry is allowed when entering an
Astro Set Point
ERR 15 A day may not be copied to itself or to a day which has
already been programmed.
ERR 16 February 29th is only permitted in leap year
ERR 17 No circuit selected–select a circuit using the circuit
enable switches
ERR 18 Astro entry is out of limits–SUNRISE must be before
noon and SUNSET must be after noon. SUNSET must
not be within 5 hours of SUNRISE.
ERR 19 The date does not agree with the previously entered
day of the week–review and correct one of the entries.
ERR 20 Holidays may not end before they start and they must
end by Dec. 31.
ERR 21 The selected holiday has already been used–Press
REVIEW to see its definition.
ERR 22 HOLIDAY PROGRAM must be cleared before
clearing holiday number.
ERR 23 Copied to days may be cleared but may not be copied
or changed.
ERR 0A HOLIDAY entry not applicable
ERR 0b Override entry not applicable
ERR 0C PULSE entry not applicable
ERR 0d INTERVAL entry not applicable
36
Problem Solution(s)
Events programmed via Day Group
or Copy Day methods will not show when
reviewing individual days or vice versa.
Difficulty in When using pulsed output for switching a
Programming/ latching relay or contactor without “self-
Reviewing On/ clearing” contacts, one circuit is dedicated to
Off Latching the load Turn On Pulse and another to the
Pulse Turn Off Pulse. The pulses are created by
or turning the respective circuits On
momentarily
Output to (1 to 2 sec.). Therefore all events must be
Latching programmed and will review as On
Pulses.
Contactor The On
time(s) of the controlled load will be
Remains On shown as On
Pulses for one circuit and the Off
After an Off time(s) will review as On Pulses for the other
Pulse circuit. Note: Using the manual On/Off keys to
switch this type of contactor On or Off will not
provide the expected result and may cause
damage to the contactor coil. For this application
an external Momentary Pushbutton must be
added for both circuits. Refer to the
Programming Examples booklet for more
information.
NOTE: If you need more programming assistance, request form
#158ET9311, Programming Examples, which contains step-by-
step instructions for several complex programs.
ERROR MESSAGES
Pressing HELP when an error code is displayed will cause an error
message and recommended action to scroll on display. Press any
key to stop message and restore pre-error display.
ERR 01 Too many keys pressed or HELP key not pressed first
ERR 02 Numeric entry not applicable
ERR 03 AM - PM key entry not applicable
Next Generation
37