Setting Freeze Temperature (optional)
Overview
Freeze temperature programming will not appear unless the optional Intermatic Freeze Sensor
(178PA28A) has been installed. This is the only freeze sensor that will work with the P1353ME
Controller.
Power must be disconnected when connecting the 178PA28A sensor.
If Intermatic Freeze Sensor (178PA28A) has been installed, use the following procedure to
program freeze temperature.
Procedure
Use the <PROGRAM> button to advance to the
Freeze Temp setting, as shown. The 1st Circuit and
32°F are the factory default settings.
Use the <ARROW> buttons to modify the desired
freeze temperature trip point. The programming range
is 32° through 44° F.
After you have set the desired trip temperature, push
and release the desired ON/OFF button to indicate
which circuits should come ON when the trip temperature is reached.
When programming is complete, , press the <ENTER> button to save and exit, or the
<PROGRAM> button to save and advance to the next programming feature.
The display will look like the example shown at the
right when the Freeze Control feature is activated. In
this example, the freeze sensor was connected, enabling
the Freeze Control feature. Circuits #1 and #3 were
programmed to come on during a Freeze condition.
AUX1 and AUX3 will blink, indicating that the control
has activated these two circuits due to a freeze condition.
NOTE: You can override the circuits during a freeze condition by pressing and releasing the
corresponding ON/OFF buttons. This will turn the devices OFF. The override will only last one
hour, so if the freeze condition still exists after one hour, Circuits #1 and #3 will come back on.
NOTE: Freeze protection stays enabled until the outside air temperature exceeds the
programmed freeze temperature for more than one minute.
1.
2.
3.
4.
32°F
Freeze Temp
1st Circuit
32°F
Freeze Temp
1st Circuit
Aux #1 and #3
Freeze
Aux #1 and #3
Freeze