User's Manual Part 2
Four: Programming the Three-Circult Clock Mechanism 29
Providing a brighter solution.™
Mode 4 — (Pump High, Pump Low, Cleaner Pump)
Circuit one and two are dedicated single pole 
outputs for a two-speed pump load. Circuits one and 
two will never be ON at the same time, consistent 
with a two-speed pump application. Circuit three 
is also a dedicated single pole output for a pressure 
side cleaner pump. Circuit three will never come 
on unless circuit one is on for at least one minute, 
consistent with a pressure side cleaner pump.
Mode 5 — (Pump, Pump, Aux3)
Circuit one and two are now coupled together 
making up one circuit capable of switching the 
power source to one pump. The On/Off button for 
circuit one now controls both circuit one and two 
simultaneously. The On/Off button for circuit two is 
disabled. Circuit three remains a single pole circuit 
for a generic load, and is independent of circuits one 
and two..
Figure 4-6Figure 4-6
NOTE: This drawing illustrates 
that only one leg is broken, with 
the other leg going directly to 
load, whether 120V or 240V.
NOTE: This drawing illustrates 
that only one leg is broken, with 
the other leg going directly to 
load, whether 120V or 240V.
Figure 4-7Figure 4-7
NOTE: This drawing illustrates 
that only one leg is broken, with 
the other leg going directly to 
load, whether 120V or 240V.
NOTE: This drawing illustrates 
that only one leg is broken, with 
the other leg going directly to 
load, whether 120V or 240V.










