Program Section: P001 (Inputs)
Pxx1È00 Keypad Selections NOTE: “xx1” represents the input number.
(left to right on keypad screen) N America Example:
Pressing the keypad button under È
? will display the module the point is associated with and the module’s point
range.
Name Selections Description Regional Settings Default
Circuit Type
0: N/C (no EOL)
1: N/C with 2.2k EOL
2: Form “C” single resistor EOL
& N/O with 2.2k EOL
3: Form C—dual 2.2k
First digit of the input’s first 3
digit code for standard types
only. Refer to S007:00 for
Custom Circuit Types.
A “000” 3 digit code is an
undefined input.
Example: 201
Point Type
01 - 33: See the Input Point Type
Reference table.
80 - 99: Custom types
programmed in section: T080 -
T099.
Second 2 digits of the input’s
first, 3 digit code
A “000” 3 digit code is an
undefined input.
Example: 201
Area this input is
assigned to.
01
Buffer Area A secondary area that shares
Entry/Exit doors with the above
first area. If not a Buffer Area,
enter the same area number as
above, again here.
01
Pxx1È1 Keypad Selections (left to right on keypad screen)
NOTE: “xx1” represents the input number.
Name Selections Description Regional Settings Default
Input # 1 Label 16 available characters
The input name that will appear
in input Status, Alarm menus,
etc. Edit the same as the
Greeting Message, S001:04
Example:
FRONT DOOR
(16 available characters)
Input Point-Type Reference
Point Type (###)
Class
Monitored for these
Area Arming Level(s)
Monitoring Style
By-
pass
Chime Tx Off
Tx
Stay
Tx On
Sonlrt
Off
Sonlrt
Stay
Sonlrt
On
Siren
Off
Siren
Stay
Siren
On
01 (Entry Door) Burg Stay & On Entry/Exit Door 99 99 99 9
02 (Entry Route) Burg ON Only Entry/Exit Route 9 9 9 9
03 (Perimeter) Burg Stay & On Immediate 9 99 99 99 9
04 (Interior Motion) Burg ON only Immediate 9 9 9 9
05 (Motion–FAP) Burg ON only FAP 9 9 9 9
FAP: (False Alarm Preventer) If a FAP input is not OK longer than 10 seconds, an alarm condition occurs. If a FAP input is triggered and immediately resets, a 20
minute timer begins. If the same device is tripped or a different FAP device trips in the same 20 minutes, an alarm occurs.
06 (Day Warning) Burg 24hr Immediate 9 9 9 9 99
07 (24hr Burglary) Burg 24hr Immediate 99 9 9 9 9 9 9 9 9
10 (Fire - A) Fire-A 24hr Immediate – – 9 9 9 9 9 9 9 9 9
11 (Fire - Delayed) Fire 24hr 15s delay – – 9 9 9 9 9 9 9 9 9
12 (Fire - Immed) Fire 24hr Immediate – – 9 9 9 9 9 9 9 9 9
13 (Hold-up) holdup 24hr Immediate – – 9 9 9 – – – – – –
14 (Aux Alert) Emerg 24hr Immediate – – 9 9 9 9 9 9 9 9 9
20 (Supervisory) Spvsr 24hr Immediate 99 9 9 9 9 9 – – –
30 (Local - 24hr) Burg 24hr Immediate 9 – – – 9 9 9 9 9 9
31 (Local-Stay&On) Burg Stay & On Immediate 9 9 – – – – 9 99 9
32 (Future Use) Burg Future Use Future Use 9 9 – – – – – 9 9
33 (Local - ON only) Burg ON only Immediate 9 9 – – – – – 9 9
80 - 99 (Custom)
Custom point types as defined in T080 - T099. Custom point types provide full control over input point characteristics, plus additional
features including arm/disarm keyswitch operation, and setting up garage door sensors, Vault/Safe class input points, plus guard-tour
points, and work-late buttons.
201·01·01·········
ÈSave È? P001È00