Installation Guide Owner manual

21-3602E rev1.5 Monitor xL™ Advanced Installation Guide 53
R00107 Keypad Selections
(left to right on keypad screen) Example:
Default Name Selections Description
04 Unlock Time 00-31 (Delay Table)
04 = 5 Sec
The unlock duration when a user is
granted entry.
06
Challenged Unlock
Time
00-31 (Delay Table)
06 = 15 Sec
The unlock duration when access is
granted for a physically challenged user.
Whether or not the 'Challenged' unlock
time applies is based on the 'Challenged'
setting for the user. For details, refer to
U00102 (User Name and Basic
Settings)
0
Door Alarm
Monitoring
0=None
1=Door Held Open Processing, 2=Door
Forced processing,
3=Door Held
Open and Door Forced
Processing
Whether or not this door is to be
monitored for forced entry and/or being
held open too long.
(yes)
Reader LED Mode
= BiColor = Normal
Set this as yes for arming stations,
and for any readers with a bicolour LED.
(no)
RTE Required
(request to Exit)
(yes) (no)
Whether or not the RTE input will be
used / monitored.
(no)
Panel Process RTE
(yes) (no)
Sets the main panel to control RTE pro-
cessing instead of the door controller
(no)
Do Not Unlock Door
On Process RTE
(yes) (no)
This setting is used with "Interlocked"
doors that are equipped with an RTE
button e.g. PIR RTE. For details on the
'interlock' feature, refer to R00111
(no)
Log RTE
(yes) (no)
Whether 'RTE presses' are to be
recorded.
(no)
Turn Style
(yes) (no)
Escort can use card 2
n
d
time to enter
after using once to validate at Anti-Pass
Back door.
(no)
Entry Detection
(yes) (no)
Second try at Anti-Pass Back door if first
unlock missed. I.e. door was not opened
at 1
st
unlock.
RTE = “Request to Exit”
04· 06· 0·
·
Save R00107