Installation Guide Owner manual

21-3602E rev1.5 Monitor xL™ Advanced Installation Guide 31
Program Section: P001 (Inputs)
Pxx100 Keypad Selections Note: “xx1” represents the input number.
(left to right on keypad screen) Example:
Pressing the keypad button under
? will display the module the point is associated with and the module’s point
range.
Default Name Selections Description
Example:
2
01
Circuit Type
0: N/C (no EOL)
1: N/C with 2.2k EOL
2:
Form “C” single resistor
EOL & N/O with 2.2k EOL
3: Form C—dual 2.2k
First digit of the input’s first 3 digit code for standard types
only. Refer to S007:00 for Custom Circuit Types.
A “000” 3 digit code is an undefined input.
Example:
201
Point Type
01 - 33: See the Input Point
Type Reference table.
80 - 99: Custom types
programmed in section: T080 -
T099.
Second 2 digits of the input’s first, 3 digit code
A “000” 3 digit code is an undefined input.
01
Area this input is
assigned to.
– –
01
Buffer Area
A secondary area that shares Entry/Exit doors with
the above first area. If not a Buffer Area, enter the
same area number as above, again here.
Pxx11 Keypad Selections (left to right on keypad screen)
Note: “xx1” represents the input number.
Default Name Selections Description
Example:
FRONT DOOR
(16 available characters)
Input # 1
Label
The input name that will appear in input
Status, Alarm menus, etc. Edit the same
as the Greeting Message, S001:04
Input Point-Type Reference
Point Type (###)
Class
Monitored for these
Area Arming Level(s)
Monitoring Style
By-
pass
Chime Tx Off
Tx
Stay
Tx On
Sonlrt
Off
Sonlrt
Stay
Sonlrt
On
Siren
Off
Siren
Stay
Siren
On
01 (Entry Door) Burg Stay & On Entry/Exit Door
02 (Entry Route) Burg ON Only Entry/Exit Route
03 (Perimeter) Burg Stay & On Immediate
04 (Interior Motion) Burg ON only Immediate
05 (Motion–FAP) Burg ON only FAP
FAP: (False Alarm Preventor) If a FAP input is not OK longer than 10 seconds, an alarm condition occurs. If a FAP input is triggered and immediately resets, a 20
minute timer begins. If the same device is tripped or a different FAP device trips in the same 20 minutes, an alarm occurs.
06 (Day Warning) Burg 24hr Immediate
07 (24hr Burglary) Burg 24hr Immediate
10 (Fire - A) Fire-A 24hr Immediate
11 (Fire - Delayed) Fire 24hr 15s delay
12 (Fire - Immed) Fire 24hr Immediate
13 (Hold-up) holdup 24hr Immediate
14 (Aux Alert) Emerg 24hr Immediate
20 (Supervisory) Spvsr 24hr Immediate
30 (Local - 24hr) Burg 24hr Immediate
31 (Local-Stay&On) Burg Stay & On Immediate
32 (Future Use) Burg Future Use Future Use
33 (Local - ON only) Burg ON only Immediate
80 - 99 (Custom)
Custom point types as defined in T080 - T099. Custom point types provide full control over input point characteristics, plus additional
features including arm/disarm keyswitch operation, and setting up garage door sensors, Vault/Safe class input points, plus guard-tour
points, and work-late buttons.
2
0
1
·
0
1
·
0
1
·········
Save ? P00100