Installation Instructions

4 of 9 P/N 1069682 • REV 1.0 • ISS 14APR10
Table 1: Loop Resistance per 1000 feet
Wire Type Resistance
24 AWG /0,53 mm 52 ohms
23 AWG /0,57 mm 42 ohms
22 AWG /0,64 mm 33 ohms
Table 2: Power Distance Chart
Power Supply Voltage 12 VDC 24 VAC 28 VAC
Voltage at the Camera 10.8 VDC 21.6 VAC 21.6 VAC
Dual 24 AWG 448 ft. / 137 m 896 ft. / 273 m 2,388 ft. / 728 m
100 mA Camera
Dual 23 AWG 564 ft. / 172 m 1,130 ft. / 345 m
3,012 ft. / 918 m
Dual 24 AWG 150 ft. / 46 m 300 ft. / 92 m 796 ft. / 243 m
300 mA Camera
Dual 23 AWG 190 ft. / 58 m 378 ft. / 115 m 1,004 ft. / 306 m
Dual 24 AWG 46 ft. / 14 m 90 ft. / 28 m 240 ft. / 73 m
1 AMP Camera
Dual 23 AWG 58 ft. / 18 m 114 ft. / 35 m 300 ft. / 92 m
Important Safety Warnings
Installation should be made by a qualified service person and should
conform to all local codes.
DO NOT bundle UTP signals in the same conduit as high-voltage wiring.
To reduce the risk of fire or electrical shock, do not expose these products to
rain, moisture, dripping or splashing.
No objects filled with liquids, such as vases, shall be placed on GE equipment.
DO NOT block ventilation openings to let sufficient airflow to the UTP devices.
Only unplugging the power cord is considered as a main power disconnect.
DO NOT connect multiple outputs together.
Make sure that the mains Voltage input is set to the proper local voltage.