Installation Instructions

Page
2
Installation
Install the proximity reader next to the locking device in an unsecured area and connect the
connecting cable either directly or via an extension cable
1
to the access manager controlling
and monitoring this access point.
Installation Variants
2
1
3
A
B
1a
1
4
3
1
1a
max.
2m
4
max.
100m
5
A Connection via extension cable B Direct connection
1 Proximity reader 1 Proximity reader
1a Connecting cable 1a Connecting cable fed in an empty tube
2 Junction box with 10-pin terminal strip 3 Empty tube, max. 2m
3 10-wire cable
1
in empty tube 4 Access manager or junction box
4 Access manager, e.g. IF 0-610
5 8 mm bore for connecting cable (1a)
An at least 10-wire, shielded data cable
1
may be used to extend the available connecting
cable to a length of 100 meters/ 400 feet provided that GND and +5 VDC are connected with
two conductors each.
1
Cable type: e.g. J-Y (ST) Y 5x2x0.6mm or 10 conductor shielded cable AWG 22.