Product Data Sheet / Brochure

UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory
Description
4 post rackmount installation accessories included
Installation Form Factors Supported
with Optional Accessories
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND); 2-4 post front rail
rackmount (UPSHDEARKIT)
Primary Form Factor Rackmount
UPS Power Module Dimensions
(hwd, in.)
3.5 x 17.5 x 13.5
UPS Power Module Dimensions
(hwd, cm)
8.9 x 44.4 x 34.3
Rack Height (U Spaces) 2U
UPS Power Module Weight (lbs.) 34
UPS Power Module Weight (kg) 15.4
UPS Shipping Dimensions (hwd / in.) 9 x 24 x 20.2
UPS Shipping Dimensions (hwd /
cm)
22.9 x 61 x 51.4
Shipping Weight (lbs.) 36
Shipping Weight (kg) 16.3
Cooling Method Fan
UPS Housing Material Steel
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 100
AC Mode Efficiency Rating (100%
Load)
97%
COMMUNICATIONS
Communications Interface DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
PowerAlert Software Included
Communications Cable USB and DB9 cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
4 / 5