Service Guide
126 Intel
®
Server System SR2600UR/SR2625UR Service Guide
7. Connect the two cables to the USB and control panel connectors on the back side of
the backplane as shown (see letter “B” in Figure 121).
Figure 121. Installing Control Panel Module into the Server System
Replacing a Fan Module
See the following sections:
•
“Replacing a Redundant Fan Module” on page 128 for instructions to replace a
redundant fan module
•
“Replacing a Fixed Fan Module” on page 131 for instructions to replace a fixed fan
module
Replacing a Redundant Fan Module
To replace a redundant fan module, follow these steps:
1. Remove the PCI riser assembly. For instructions, see “Removing the PCI Riser
Assembly” on page 50.
2. Remove the processor air duct. For instructions, see “Removing the Processor Air
Duct” on page 56.
3. Remove the large air baffle. For instructions, see “Removing the Large Air Baffle”
on page 70.
4. Remove the fan baffle. For instructions, see “Removing the Fan Baffle” on page 67.
5. Remove the bridge board. For instructions, see step 5 in “Removing the Midplane
Board” on page 103.
6. Disconnect the fan cables from the midplane.
Backplane
B
A
AF003016