Design and Environmental Specifications Intel® Server Board S5500WB TPS
Revision 1.9
Intel order number E53971-008
78
Table 54. Fan Connector Location & Detail
CPU 2
Memory 2
FAN_CPU2
FAN_CPU2A
FAN_MEM2
FAN_MEM2R
PWM_CPU0
PWM_CPU0
PWM_MEM0
PWM_MEM0
Tach 3
Tach 7
Tach 4
Tach 4 & 8
J3E1
J2J2
J2J1
J1D5
LED_Fan_Fault_CPU0
LED_Fan_Fault_CPU0A
LED_Fan_Fault_MEM0
LED_Fan_Fault_MEM0R
Figure 29. Fans and Sensors Block Diagram
9.2 Thermal Sensors
9.2.1 Processor PECI Temperature Sensor
The processor thermal control uses a CPU PECI thermal sensor, which is a relative
temperature off PROCHOT# trip point (a -20C reading means 20C below PROCHOT# trip point
temperature). The BMC can get the processor PECI Tcontrol values for each CPU installed to
use/follow the clamped algorithm for component thermal sensor. The following sample SDR
settings could be used:
Use Tcontrol (byte 8, bit 0 = 1): Tcontrol value is provided by BIOS via the Set CPU
TControl command for the indicated CPU is used.