Technical Product Specification
Environmental Specifications Intel® Server System R1304BTSSFAN/ R1304BTLSFAN/ R1304BTLSHBN TPS
11. Environmental Specifications
11.1
System Level Environmental Limits
The following table defines the system-level operating and non-operating environmental limits.
Table 31. System Environmental Limits Summary
Parameter
Limits
Operating Temperature
+10°C to +35°C with the maximum rate of change not to exceed 10°C per hour
Non-Operating
Temperature
-40°C to +70°C
Non-Operating Humidity
90%, non-condensing at 35°C
Acoustic noise
Sound Power: 7.0 BA in an idle state at typical office ambient temperature (23 +/-
2°C)
Shock, operating
Half sine, 2g peak, 11 msec
Shock, unpackaged
Trapezoidal, 25g, velocity change 136 inches/sec (
≧
40 lbs to > 80 lbs)
Shock, packaged
Non-palletized free fall in height 24 inches (
≧
40 lbs to > 80 lbs)
Vibration, unpackaged
5 Hz to 500 Hz, 2.20 g RMS random
ESD
+/-12kV for air discharge and 8K for contact
System Cooling
Requirement in BTU/Hr
1660 BTU/hour
Airflow, operation
Performance: 45 CFM
Idle: 25 CFM
Disclaimer Note: Intel ensures the unpackaged server board and system meet the shock
requirement mentioned above through its own chassis development and system configuration. It
is the responsibility of the system integrator to determine the proper shock level of the board
and system if the system integrator chooses different system configuration or different chassis.
Intel Corporation cannot be held responsible, if components fail or the server board does not
operate correctly when used outside any of its published operating or non-operating limits.
Revision 2.4
34