Server System R2000GZ/GL Product Family TPS
4.3 System Fans
Five 60x38-mm fans and an embedded fan for each installed power supply, provide the primary airflow for the
system. The following table provides the volumetric air flow requirements for different 2U system
configurations.
Table 25. 2U System Volumetric Air Flow Requirements
System Configuration
Air Flow Range (CFM)
3.5” x 12 drives
20 96 CFM
2.5” x 24 drives
26 113 CFM
All other 2U system configurations
1180 CFM
The system is designed for fan redundancy when configured with two power supply modules. Should a single
fan fail (system fan or power supply fan), platform management will adjust air flow of the remaining fans and
manage other platform features to maintain system thermals. Fan redundancy is lost if more than one fan is in
a failed state.
Figure 23. System Fan Identification
Revision 2.2