Generators and Extension Cords
GENERATORS AND EXTENSION CORDS
18
Your FORCE/2 will operate on power from a commercial-sized generator. No
household generators may be used due to the high inrush requirements of the
FORCE/2.
Also, generators made by Honda, Yamaha, Coleman
and Generac are not recommended.
While they are of high quality,
these generators do not have the inrush protection devices necessary to start the
FORCE/2 and protect the generator. The start-up requirement for a FORCE/2
is 9660 w
atts; normal operating requirement is 3300 watts.
W
e recommend
a generator of not less than 9000 watts,
120 VAC. In addition, Intec
recommends generators that have a 50% power boost feature which aids the
generator in high current startups.
Running additional equipment from the same generator means you will need to
know the total electrical requir
ements before selecting the correct size of
generator. For details on selecting and purchasing a generator, please call
INTEC.
Note: Using a generator of insufficient size will void your Warranty.
Adding Additional Power Cords.
Wire
Size
A
W
G
10
12
14
16
18
3
Conductor
Amps
25
20
15
10
7
4
Conductor
Amps
20
15
12
8
6
Cord Current Capacities, Type S & SVT
The length of cord and ambient temperature does have an effect on the
electrical current capacity. Consult Intec for your specific needs or your local
electrical distributor.