Installation Instructions
11.1.19 357-05366-02 Rev A © Inovonics, 2019 - www.inovonics.com 2
2.6 Mount the Transmitter
1. Attach the mounting bracket to the wall, using either screws or double-
sided tape.
Note: There are two mounting holes for standard installation. An optional
third mounting hole is located under the battery. Use the third mounting
hole to secure the housing to the bracket.
2. Hook the bottom of the transmitter into the bracket’s bottom catch, and
press the transmitter into the bracket so that the bracket’s top lip snaps
into place.
3 Specifications
Dimensions: 3.5” x 1.7” x 0.9”.
Typical battery life: 8 years at a 5 minute transmission interval.
Battery type: Panasonic CR123A or equivalent.
Operating environment: -4° to 140°F.
Operating humidity: 0 to 90%, non-condensing.
Temperature measurement: Internal measurement transmitted as:
Fahrenheit or Celsius; internal measurement range: -13° to 140°F; typical
accuracy: 0.8°F at room temperature.
External measurement: Transmitted as: temperature or resistance; external
thermistor temperature range: -22° to 212°F; external thermistor resistance
range: 100 to 250,000 ohms; typical external resistance measurement
accuracy: + or - 1% from 100 ohms to 500 ohms, + or - 0.5% 500 ohms to
250K ohms.
Configuration options: Measurement intervals: 0.5, 1, 5, or 30 seconds, 1,
5, or 15 minutes, or only on transmit; transmission intervals of 10 or 30
seconds, 1, 2, 5, 10, 15 or 30 minutes; Delta T value of 0.5, 1, 5, or 10
degrees or % resistance (Delta T can be disabled).
System requirements: Requires use of the EN4000 serial receiver and an
application designed to support advanced functionality.
Operating frequencies: EchoStream: 902 - 928 MHz North America, 915 -
928 MHz Australia, 922 - 928 MHz New Zealand.
Regulatory compliance: FCC; RoHs compliant; Industry Canada; RCM.
Note: The transmitter output power level is the same for North America,
Australia and New Zealand.
Note: Inovonics supports recycling and reuse whenever possible. Please
recycle these parts using a certified electronics recycler.
Note: Specifications and data are subject to change without notice.
Caution: Changes or modifications not expressly approved by Inovonics
could void your authority to operate the equipment.
4 Television and Radio Interference
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance
with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
5 FCC Part 15 and Innovation, Science and
Economic Development Canada (ISED)
Compliance
This device complies with part 15 of the FCC Rules, and ISED license-
exempt RSS standard(s). Operation is subject to the following two
conditions: (1) this device may not cause interference, and (2) this device
must accept any interference that may cause undesired operation of the
device.
Le présent appareil est conforme aux CNR Innovation, Sciences et
Développement économique Canada applicables aux appareils radio
exempts de licence. L'exploitation est autorisée aux deux conditions
suivantes: (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur
de l'appareil doit accepter tout brouillage radioélectrique subi, même si le
brouillage est susceptible d'en compromettre le fonctionnement.
6 Radiation Exposure Limits
6.1 FCC
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment. In order to avoid the possibility of exceeding the
FCC radio frequency exposure limits, human proximity to the antenna shall
not be less than 20 cm during normal operation and must not be co-located
or operating in conjunction with any other antenna or transmitter.
6.2 ISED
This equipment complies with ISED RSS-102 radiation exposure limits set
forth for an uncontrolled environment. This transmitter must be installed to
provide a separation distance of at least 20 cm from all persons and must
not be co-located or operating in conjunction with any other antenna or
transmitter.
Cet équipement est conforme avec ISED RSS-102 des limites d'exposition
aux rayonnements définies pour un environnement non contrôlé. Cet
émetteur doit être installé à au moins 20 cm de toute personne et ne doit
pas être colocalisé ou fonctionner en association avec une autre antenne
ou émetteur.