User's Manual
D-4 Appendix Installation Manual
Lock Operation Verification
From Controller:
1. Verify 12V AC output at P10
2. Label and remove wires in P4
connector
3. Jumper “Fire +V In” to “Fire +V Out)
4. With a Tag in monitored zone, use an
ohmmeter to check for a closed contact
across “Lock N.O.” and “Lock Comm”
5. When you remove Tag from zone, this
contact should then open
6. If these actions do not occur then the
Controller board is defective
7. If board tests good, continue to
“At Lock:”
At 3101 Lock:
1. Verify 12V AC at Pins 1 & 2
(Green LED1 should be on in non-
energized state)
2. Using a jumper wire or needle-nose
pliers, jumper Pin 3 to Pin 4.
(This should energize the Lock; the
Green LED1 will change to Red)
3. Use a jumper wire or needle-nose
pliers to short Pins 5 & 6.
(This will de-energize or reset Lock;
LED1 will turn off for as long as pins 5
& 6 see a closed contact)
4. NOTE: LED2 should be lit at all times,
if it is flashing or not illuminated then
the Lock board is defective.