User's Manual
2-4 Wire and Cables Installation Manual
Table 2.2 Wire Gauge Table - For common system devices
The following table indicates the recommended minimum wire gauge for a given length of cable. This table reflects
the fact that there are two conductors, power and ground, running to each device.
Note: 1000 feet of cable means the supply current travels a total of 2000 feet.
Supply
Voltage
(DC)
V
Min.
Peripheral
Device:
Current
@12V
AC/DC
1’-
25’
25’-
100’
100’-
250’
250’-
500’
500’-
1000’
1000’-
000’
12V 10V
Local Alarm
12mA 24 24 24 24 24 24
12V 9V
Central
Alarm
100mA 24 24 24 22 18 16
12V 9V
Keypad
55mA 24 24 24 24 22 20
12V 9V
Keypad
w/ PBO
75mA 24 24 24 24 22 18
12V 6V
Magnetic
Switch
25mA 24 24 24 24 24 18
12V 9V
SAP
150mA 24 24 24 24 24 18
12V 9V
GDP
500mA 24 24 24 24 24 18
12V 9.5V
PIR
10mA 24 24 24 24 24 18
12V 11V
Multiplexer
500mA 18 18 18 18 18 16
12V 9V
Elevator
Deactivation
Relay
100mA 18 18 18 18 18 18
12V 10.5V
3000/3101
Lock*
450mA 18 18 18 18 16 12
12V 10.5V
3000/3101
Lock**
900mA 18 18 18 16 12 10
*This is for one lock, receiving 12VAC from the Controller.
**This is for two locks, in parallel, receiving 12VAC from the same Controller.