User's Manual

Installation Manual The Accutech Systems 1-3
An optional Loiter function is available to alert
staff personnel if a Tag is in a monitored zone
(even if the door or elevator is closed) for too
long. The time setting is adjustable (10-110
seconds) and is factory set for 15 seconds.
An optional Door Ajar function is also available
to alert staff personnel if the door in a monitored
zone has been held open for too long. The time
range can be set for immediate or from 10 to 110
seconds and is factory set for approximately 15
seconds.
Elevators
Elevator Deactivation Circuitry is needed to
restrict the operation of a monitored elevator
from a Tag.
If a Tag enters a monitored elevator zone (with
Elevator Deactivation Circuitry), the elevator’s
call button will be deactivated for as long as the
Tag is in the zone.
If the elevator car is en route to that floor and the
door(s) open (or if the elevator car door is
already open at that floor when a Tag
approaches), the system will go into alarm and
will not allow the elevator doors to close until a
valid code is entered into the zone’s Keypad.
If you wish to escort a Tag through a monitored
elevator zone, push the call button while the Tag
is out of the zone and wait for the car to arrive
(when the elevator bell rings). Enter a valid code
into the zone’s Keypad. Then escort the Tag to
the elevator door and you will be able to move
the Tag between floors using the elevator.
Hallways
If a Tag enters a monitored hallway zone, the
system will detect the Tag and the PIR will
detect motion. The system can then sound
alarms, trigger visual displays and, in special
circumstances, lock nearby doors.
If you wish to escort a Tag through a monitored
hallway zone, you will need to enter a valid code
into the zone’s Keypad to activate the Escort
function. This will silence alarm and allow the
Tag the pass through the monitored hallway
zone for the designated Escort time. The
duration of the Escort function is adjustable
from 0 to 98 seconds.
Alarms
In this manual, Egress alarms are referred to as
“Alarms.” These alarms do not automatically
reset once the Tag leaves the monitored zone or
the door has been closed. They are “latched”
once they have been triggered. This has been
done, by design, to ensure that all alarm
conditions are investigated and corrected by
facility staff.
An alarm (i.e., an Egress alarm) occurs
whenever a Tag enters a monitored zone and the
door is opened or a PIR is triggered. To clear
this alarm remove the Tag from the zone, close
the door and enter a valid code into the Keypad.
Other alarm types are referred to by name in this
manual. These alarms can be automatically reset
once the condition(s) causing the alarm have
been corrected.
A Door Ajar alarm occurs when a door is open
for longer than the preset time. The door must be