User's Manual
1-2 The Accutech Systems Installation Manual
IS 3200 System
The IS 3200 System is the ES 2200 System plus
a computer with the Accutech Software
installed, a TAD, a Tag Test Station, a
Multiplexer, a Power Supply.
The IS 3200 System uses IS 3200 System Tags
(
LT/SB32) that are placed on the monitored
resident or asset. Once assigned, the computer
associates a name, room number and any other
pertinent information about the resident/asset
with that Tag.
BR 4200 System
The function of the BR 4200 and System is to
alert facility personnel of the possible abduction
of an infant.
The BR 4200 System is the IS 3200 System plus
BR 4200 Auxiliary Receivers (as needed) and an
additional alarm to announce when a band
removal incident has occurred.
The BR 4200 System uses BR 4200 System
Tags (
BR42) that are placed on infants. In
addition to the functionality of an IS 3200
System Tag, the BR 4200 System Tag will
trigger alarms (visual and/or audial) if the band
is removed or tampered with in any way to alert
facility personnel of a possible infant abduction
attempt.
Cut Band System
The function of the Cut Band System is to alert
facility personnel of the possible adduction of a
child. The Cut Band System is the BR 4200
System with Cut Band Tags, which will trigger
alarms (visual and/or audial) if the band is cut.
How Accutech Systems Work
Doors
Elevators
Hallways
Alarms
This section explains how Accutech Systems
react to a Tag entering a monitored door zone, a
monitored elevator zone, and other alarm events.
NOTE: In this manual, Egress alarms are
referred to as “Alarms.” Other alarm types are
referred to by name (i.e., door ajar, loiter,
supervise, band removal).
Doors
When a Tag enters a monitored door zone, the
system will detect the Tag. At that moment
(providing the door has the Magnetic Lock
option, the door is closed, and the Lock is
unobstructed) the doors will lock and will
remain locked as long as the Tag is in the
monitored door zone. When the Tag leaves the
monitored zone, the door will unlock after an
adjustable period of time.
If a Tag enters a monitored door zone (with or
without the Magnetic Lock option) and the door
is already open (or is opened while the Tag is in
the zone), the Accutech System will go into
alarm.
If you wish to escort a Tag through a monitored
zone, you will need to enter a valid code into the
zone’s Keypad to activate the Escort function.
The Keypad’s Escort function will release the
Magnetic Lock, silence alarms, and allow the
Tag to pass through the monitored door zone for
the designated Escort time. The duration of the
Escort function is adjustable from 0 to 98
seconds.