User's Manual
Installation Manual Automatic Door Deactivation 16-1
Automatic Door Deactivation
In automatic door applications (doors that open
via a motion sensor or push paddle), the
Accutech System can deactivate this feature
when a Tag enters monitored zone’s Tx
Activation Field.
Wiring Automatic Door Deactivation
To wire the Controller for Automatic Door
Deactivation, refer to Figure 16.1 and use the
following instructions:
1. On the Controller, jumper pins 1
(+V Out) and 2 (Call Comm) of P3.
2. Connect pin 1 (Call N.O) of P3 to the
positive (+) of the 12V DC Relay.
3. Connect pin 5 (Ground) of P7 to the
negative (-) of the 12V DC Relay.
4. Connect 4 (N.O.) and 7 (Comm) to the
door equipment.