User's Manual
15-2 Perimeter Functions Installation Manual
Temperature
The Timer operates best in an ambient
temperature between 35 and 90 degrees
Fahrenheit. Operation outside of this range may
cause unexpected or undesirable results,
including premature failure.
Weight
The Timer (including cabinet) weighs 2 U.S.
pounds.
Positioning and Mounting the Timer
It is best to position the Timer near the
Controller that it will interface with. Use
hardware appropriate for the weight, size and
mounting surface when mounting the Timer.
Connecting the Timer
You will need 18-gauge, 4-conductor Plenum-
rated cable for installation.
To connect the Timer to the Controller, refer to
Figure 15.2 and use the following instructions:
1. Using the BLACK wire, connect the “-“
pin of the Timer to P9-pin6 (Ground) of
the Controller.
2. Using the RED wire, connect the “+”
pin of the Timer to P9-pin1 (+12V) of
the Controller.
3. Using the WHITE wire, connect the
“N.O” pin of the Timer to both P6 pins
of the Controller.
4. Using the GREEN wire, connect the
“C” pin of the Timer to P9-pin1 (+12V)
of the Controller.
Figure 15.2 Connecting the Timer