At the Second Condition Source:
If the second condition source is provided by the
elevator controls, Use the previously wired
terminals on the 4- position screw terminal strip
in the Elevator Deactivation Relay cabinet to
hookup to the dry contract.
If the second condition source is a locally
mounted Magnetic Switch or a Passive Infrared
Reader (PIR) unit, wire them to the Controller.
Summary of Elevator Deactivation
for the Elevator Company
Call Button Deactivation
Elevator Car Deactivation
The following is a brief summary of Elevator
Deactivation that can be given to the Elevator
Company.
Call Button Deactivation
When a Tag is detected in the monitored
Elevator zone, the Accutech system energizes
Relay K2 and the Call Button for that Elevator
zone is deactivated.
When the K2 Relay is de-energized, the Call
Button is reactivated.
Elevator Car Deactivation
When a Tag is detected in the monitored
Elevator zone and the second condition is met,
the Accutech System energizes Relay K1.
If the elevator car is at the floor (with doors
open) the elevator will be deactivated.
If the elevator car is on its way to that floor, it
will continue to that floor and upon arrival (with
doors open) will be deactivated.
As long as relay K1 is energized, the elevator
doors will remain open preventing the car from
leaving the floor.
When Relays K1 is de-energized, the Elevator
will return to normal operation.