User's Manual

Installation Manual Alarm Output Devices 13-9
Connecting an ESGDP
(ES 2200 systems only)
To connect an ESGDP, refer to Figure 13.10 and
use the following instructions:
1. Connect the “+12V” and “Ground” from
the ESGDP to their respective pins on
the Power Supply.
2. For each Controller linked to the
ESGDP, connect all data pins of P9
(except +12V) to their respective pins
on a zone connector of the ESGDP.
NOTE: Up to 8 Receivers (i.e., 8 zones)
can be linked to a ESGDP.
3. Connect the “Fire” from the ESGDP to
the Fire Panel Interface (FPI) or the
facility Fire Panel.
Connecting a GDP
NOTE: To use a GDP in an ES 2200 system,
you will need to replace your ES 2200
Receivers. Contact your Accutech
Representative for more information.
NOTE: Up to 16 Receivers (i.e., 16 zones) can
be linked to a single GDP board. Multiple GDP
boards can be housed within a GDP frame. If
more than one GDP board is present, perform all
steps on GDP board 1.
To connect a GDP, use the following
instructions.
Refer to Figure 13.11 for steps 1-3.
1. Connect the “+12V” and “Ground” from
the GDP to their respective pins on the
Power Supply.
2. For each Receiver linked to the GDP,
connect the “Status” and “GND” pins of
P2 to a zone data input of the GDP.
3. Connect the “Fire” from the GDP to the
Fire Panel Interface (FPI) or the facility
Fire Panel.
BR Alarm filtered by HUB
*Required for All BR Systems
Refer to Figure 13.12 for steps 4-10.
4. Remove jumper JP7 from the GDP.
5. Remove jumper between “INT” and
“FROM HUB” on P7 of the GDP.
6. Connect P15-4 (Alarm N.O.) to
P12-1 (+V) of the Multiplexer
or
to 12V DC of the Power Supply.
7. Connect “IN-9-10”-Pin6 (C 3-4) to
P12-2 (-V) of the Multiplexer
or
to GND of the Power Supply.
8. Connect the COM of the Momentary
Push Button to “IN 9-10”-Pin5 (GP4) of
the GDP.
9. Connect the N.O. of the Momentary
Push Button to P1 (+12V) of the GDP.
10. For connections to a Multiplexer, see
page 17-4.