User's Manual
Installation Manual Fire Panel Interface (FPI) 12-1
Fire Panel Interface (FPI)
In addition, the FPI unit can provide:
FPI Specifications
An Optional Central Override, which
allows the facility to disable all Locks
and/or Elevator Deactivation units
controlled by that FPI. Each FPI
requires its own override switch.
Positioning the FPI
Before Connecting the FPI
Connecting the FPI to the Controller
State codes require that all Lock and Elevator
Deactivation Circuitry be wired into the
facility’s fire alarm system.
A Manual Reset, which will re-engage
the Locks and/or Elevator Deactivation
units after the fire alarm is reset. This
switch can be replaced with a jumper
that will make the reset process
automatic once the fire alarm is reset.
This is done so that in case of a fire, any Lock or
Elevator Deactivation unit disengages, allowing
for free egress or ingress. For more information
on this policy, check your local codes.
For each FPI unit (
Figure 12.1) used, you will
need one set of dry contacts from the facility’s
fire panel. Each FPI unit provides dry contact
outputs for up to 8 Controllers.
An Auxiliary Output (+12VDC) for
alerting staff that the Locks and/or
Elevator Deactivation units are
disengaged. This is typically connected
to the Staff Alert or Graphic Panel(s).
Figure 12.1 The FPI with cabinet