LC 1200 Manual External Sounders 8-3
Specifications
Power Requirements
Temperature
Weight
Power Requirements
12 or 24V DC
Temperature
The MTLA operates best in an ambient
temperature between 35 and 90 degrees
Fahrenheit. Operation outside of this range may
cause unexpected or undesirable results,
including premature failure.
Weight
A MTLA weighs approximately 0.5 pounds.
Mounting
A MTLA is capable of being mounted to a
standard 4” x 4” or 1-1/2” back box or a single
gang 2” x 4” 1-7/8” back box.
Wiring
You will need 22-gauge, 2-conductor plenum-
rated cable for this connection.
To wire the MTLA to the LC unit, refer to
Figure 8.4 and use the following instructions:
1. Using the RED wire, connect the
positive (+) terminal of the MTLA to
P2-5 (NC) of the LC unit.
2. Using the BLACK wire, connect the
negative (-) terminal of the MTLA to
P3-4 (Ground) of the LC unit.
3. Jumper P2-6 (Alarm Comm) to P3-3
(+12V DC) on the LC unit.
Figure 8.4 Wiring the MTLA