User Manual

LC 1200 Manual System Maintenance & Testing 15-5
6. To reset the zone, enter a Keypad reset,
deactivate the test Tag, and, if
necessary, clear the alarm on the PC.
Zone, Elevator Deactivation Test
When a Tag approaches an elevator zone the
elevator call buttons will be disabled. This test
will evaluate this operation.
1. Notify staff and security that you will be
testing zone performance and alarms
will be generated. They should pay
special attention to traffic during this
time.
2. Using a TAD, activate the test Tag.
3. Enter the elevator zone. The zone’s
response will depend on the state of the
elevator door(s):
a. Elevators with door(s) open will
disable as you approach and an
alarm will sound. The car will not
be able to leave the floor.
b. Elevators with door(s) closed will
have their call button(s) disabled.
c. Elevators en route will arrive, open,
and then an alarm will sound. The
car will not be able to leave the
floor.
4. Record the results (pass or fail)
5. If the test fails to cause an alarm:
a. Notify staff and security of the
vulnerable area.
b. Check for visible damage or
tampering to the zone equipment.
c. Have a maintenance technician
verify power to the zone equipment
d. Have a maintenance technician
verify the FPI is set properly
e. Call your Accutech Representative.
6. To reset the zone, deactivate the test Tag
and, if necessary, enter a Keypad reset
and clear the alarm on the PC.
Zone, Automatic Door Deactivation Test
When a Tag approaches an automatic door
deactivation zone, the motion detector and/or
push paddle will be disabled be disabled. This
test will evaluate this operation.
1. Notify staff and security that you will be
testing zone performance and alarms
will be generated. They should pay
special attention to traffic during this
time.
2. Using a TAD, activate the test Tag.
3. Enter the automatic door deactivation
zone. The door’s motion sensor or push
paddle is disabled.
4. Record the results (pass or fail)
5. If the test fails to cause an alarm:
a. Notify staff and security of the
vulnerable area.
b. Check for visible damage or
tampering to the zone equipment.