14-2 Alert Panels LC 1200 Manual
Mounting
To mount a SAP, use the following instructions:
1. Remove the front panel from its frame.
2. Using the SAP frame as a template,
mark the four mounting holes on the
mounting surface.
3. Drill the mounting holes.
4. Secure the SAP frame to the mounting
surface using appropriate hardware and
replace the front panel.
Wiring
You will need 22-gauge, 6-conductor plenum-
rated cable for this connection.
To wire a SAP to an LC unit, refer to Figure
14.2 and use the following instructions:
1. Run a separate 6-conductor unshielded
cable for each SAP that is connecting to
an LC unit. The wire gauge will be
based upon the distance it will run. On
the SAP panel, P1 is for Zone 1, P2 is
for Zone 2 and so on.
2. For each zone, connect the appropriate
alarm outputs into their respective pins.
3. A SAP only needs the use of 2 of these
wires for all but one zone. That zone
will be the one that provides power to
connector labeled P9 near the bottom of
the SAP circuit board.
4. If you have locks or elevator
deactivation, you need to run a single
conductor cable from the Fire Panel
Interface (FPI) for the fire alarm
indicator.
5. For systems that do not have restraints
(Magnetic Locks, Elevator Deactivation,
or Automatic Door Deactivation) a Fire
Panel Interface (FPI) is not necessary
unless you want Fire Alarm notification
on the SAP/GDP.
6. Remember SAPs, GDPs, and FPIs must
be powered separately from an LC unit.