User Manual

E 5 2 7 D a t a s h e e t P a g e 5 o f 7
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to
the following two conditions: (1) this device may not cause interference, and (2) this device must
accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d’industrie Canada applicables aux appareils radio exempts de licence.
L’exploitation est autorisée aux deux conditions suivantes: (1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur
de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le
fonctionnement.
RS485
A Deep Mesh RS485 (DM485) network typically uses a CAT5-type wiring wired as a home-run or daisy-chain.
The DM485 network is routed to a dedicated device in each guestroom. This device becomes the room gateway,
which transfers information packets between the DM485 backbone and the in-room network. The in-room
network can be either S5Bus or a local mesh formed with RF. Each DM485 network is operated by a B575
hardware running DM485 software. Refer to the H6 pinout table above for wiring instructions.
Technical Specifications
Power Requirements 12VDC, 50mA
Thermostat Measurement Range 33 to 99 degrees F (1 to 37 degrees C)
Outdoor Air Temperature Display 0 to 99 degrees F (-18 to 37 degrees C)
Display Resolution Whole degree F, 0.5 degree C (0.1 degree F in test mode)
Standard Deadband 2 degrees F (1 degree C) between heating and cooling
Degrees C/Degrees F Display Toggle Button located on front display
Ambient Operating 41 to 149 degrees F (5 to 65 degrees C), 0-95% RH noncondensing
Ambient Storage 33 to 149 degrees F (1 to 65 degrees C)
Dimensions 3.5” W x 3.5” H x 0.9” D (89 mm x 89 mm x 23 mm)
Approvals FCC, CE Mark
Figure 4 E527 Dimensions