Load Specifications
The following load specification table (Table 6) describes the submitted load characteristics for testing and UL
certification of UL 873. The device complies with the requirements of CAN/CSA C22.2 No. 24-93.
Table 6. Load Specifications
MODEL e528-A2L2-I0P0-
00WH
e528-A3L2-I0P0-
00WH
e528-A1L2-
I0P0-00WH
e528-B0L2-
I0P0-00WH
e528-C0L2-
I0P0-
00WH
e528-B1L2-I0P0-
00WH
Voltage 24VAC 24VAC 24VAC 100-240VAC 220-
277VAC
100-277VAC
Heat
Relay K4-5
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
240 VA PD 240 VA PD 240 VA PD 3 amps
125-277VAC
General purpose
Cool
Relay K4-5
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
240 VA PD 240 VA PD 240 VA PD 3 amps
125-277VAC
General purpose
High Fan
Relay K1
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
2.2 FLA
13.2 LRA
3.6 FLA
21.6 LRA
3.6 FLA
21.6 LRA
3.6 FLA
21.6 LRA
Medium Fan
Relay K2-3
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
Low Fan
Relay K2-3
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
Figure 8 Electrical Box Connections 24VAC