ITC-608T Manual
The Manual Is Divided Into 6 Parts.
Part 1 Quick Guide to Use 1.CAUTION: KEEP CHILDREN AWAY TO REDUCE THE RISK OF ELECTRIC SHOCK, USE ONLY INDOORS RISK OF ELECTRIC SHOCK. DO NOT PLUG INTO ANOTHER RELOCATABLE POWER TAPS OR AN EXTENSION CORD. USE ONLY IN DRY LOCATION 2.Quick Guide The instruction manual will skip to the corresponding page according to the probe you select.
Part 5 ITC-608T HUMIDITY Humidity Control Mode Controller Manual Equivalent to IHC-200 Humidity Controller Manual ITC-608T + Humidity Probe PAGE 36 Part 6 ITC-608T TEMPERATURE HUMIDITY Temperature and Humidity Control Mode Controller Manual Equivalent to IHC-230 Temperature & Humidity Controller Manual ITC-608T + Temperature Probe +Humidity Probe PAGE 43 3.
Relative humidity measurement accuracy(10%~95%RH): Typical value±3%RH, Maximum value±5%RH Display unit:temperature:Celsius °C or Fahrenheit °F; humidity:%RH Ambient Ambient temperature:-20°C~60°C/-4°F~140°F Storage environment:temperature:0°C~60°C/32°F~140°F; humidity:20~80%RH(Unfrozen or condensation state ) Warranty Controller: Two years warranty Temperature and Humidity Probe: One year warranty 4. Technical Assistance and Warranty 4.
Part 2 ITC-608T TEMPERATURE Controller Manual Equivalent to ITC-308 Temperature Controller Manual 4
1 Get to Know the Controller A WORK1 WORK2 B 86.8 96.
A Functions on screen PV:In normal mode, the measured temperature is displayed. In settings mode, it will display menu code. SV:In normal mode, the temperature setting value is displayed. In setting mode, it will display the setting value. B Output(WORK1/WORK2) Instruction WORK1: The heating output WORK2: The cooling output C Indicator LED: ●Red LED is on WORK1 output is on. ●Green LED is on WORK2 output is on. ●Green LED is blinking WORK2 output is performing the function of compressor delay.
2 Button Operation Instructions 2.1 Restore Default Settings Press the “ " button to power on, the buzzer will make a short call, indicating that all parameters of the user's temperature probe function return to the default setting value. 2.
3 Menu Instruction 3.1 Setting mode Flow Chart Press "SET" Key for over 2 seconds to enter parameters setting mode SET TS 77.
3.2 Setting Menu Instruction Code Function TS tS Temperature Setting Value HD H Heating Difference Value CD C AH AH AL AL PT P Compressor Delay 0 ~10 minutes CA CA Temperature Calibration - 9.9 ℃~ 9.9 ℃ 0.0 ℃ -15.0 ℉ ~15.0 ℉ 0.0 ℉ CF CF Fahrenheit or Celsius Setting C or F Timer Setting 0 、1 or 2 TR Cooling Difference Value Alarm High Temperature Value Alarm Low Temperature Value Setting Range Default Settings Symbol -40.0℃~100℃ 25.0 ℃ -40.0℉~212℉ 77.0 ℉ 0.3℃~15.
the green led is off and the WORK2 output turns off. For example, setting TS=25.0°C, CD=2.0°C, HD=3.0°C, when the measured temperature value ≤ 22°C (TS-HD), the controller will enter the heating state; when the measured temperature value ≥ 25°C, the heating will stop; when the measured temperature value ≥27.0°C(TS+CD),the controller enter the cooling state; when measured temperature value ≤ 25.0°C, cooling will stop. 4.1.
4.3 Compressor Delay Time(PT) In the cooling mode, when the power is turned on for the first time, PV(measured temperature value) ≥ TS(Temperature setting value) + CD(Cooling difference value), it will not start cooling immediately, but waiting for a delay time(PT).
Part 3 ITC-608T PROGRAMMABLE TEMPERATURE Controller Manual Equivalent to ITC-310T-B Temperature Controller Manual 12
1 Get to Know the Controller A WORK1 86.8 96.
A Functions on screen PV:In normal mode, the measured temperature is displayed. In settings mode, it will display menu code. SV:In normal mode, the temperature setting value is displayed. In setting mode, it will display the setting value. B Output(WORK1/WORK2) Instruction WORK1: The heating output WORK2: The cooling output C Indicator LED ●Red LED is on WORK1 output is on. ●Green LED is on WORK2 output is on. ●Green LED is blinking WORK2 output is performing the function of compressor delay.
2 Button Operation Instructions 2.1 Restore Default Settings Press the " " button to power on, the buzzer will make a short call, indicating that all parameters of the user's temperature probe function return to the default setting value. 2.2 Start Controlling Temperature from the First Stage Forcibly When TR=1 or 2, press the increase button “ ”to power on, the buzzer will make a short call, indicating the user that will start controlling temperature from the first stage forcibly. 2.
increase or decrease the temperature setting value, then press "SET" button to confirm and exit. When TR=1 or 2,SV shows the temperature setting value and flashes, then short press “ ” or “ ” button to increase or decrease the temperature setting value. Long press the“ ” or “ ”button to increase or decrease the temperature setting value quickly. Press the "SET" button to switch to the current stage control duration value. Short press the “ ”or “ ” button to change the current stage control duration value.
3 Menu Instruction 3.1 Menu Setting Flow Chart Press "SET" Key for over 2 seconds to enter parameters setting mode TR = 0 ? N SET Y SET TS 77.0℉ SET Temperature Setting Value SET SET HD Heating difference value SET SET CD SET Cooling difference value Alarm High Temperature Limit SET AH SET SET SET AL Alarm Low Temperature Limit N Cycle Mode 1~999, MD=0 Infinite Cycle AT 0 After the power off, re - running mode: 0-> manual, 1-> automatic STT 1 SST 1 S01 77.
3.2 Setting Menu Instruction Symbol Function Setting Range Default Settings TS tS Temperature Setting Value -40.0℃~100℃ 25.0℃ -40.0℉~212℉ 77.0℉ HD H Heating Difference Value 0.3℃~15.0℃ 2.0℃ 1.0℉~30.0℉ 3.0℉ CD C Cooling Difference Value 0.3℃~15.0℃ 2.0℃ 1.0℉~30.0℉ 3.0℉ AH AH Alarm High Temperature Value -40.0℃~100℃ 100℃ -40.0℉~212℉ 212℉ AL AL Alarm Low Temperature Value -40.0℃~100℃ -40.0℃ -40.0℉~212℉ -40.0℉ Code Annotation ℉ More details on 4.1 ℉ ℉ More details on 4.
U09 U09 S10 H10 S10 H10 U10 U10 S11 H11 S11 H11 U11 U11 Whether to Alarm after the Completion of Stage 9 n *** Stage 10 Temperature Setting Value Stage 10 Control Duration Value Whether to Alarm after the Completion of Stage 10 25.0℃ or 77.0℉ 10 * ** n *** Stage 11 Temperature Setting Value Stage 11 Control Duration Value Whether to Alarm after the Completion of Stage 11 25.0℃ or 77.0℉ 10 * ** n *** S12 S12 Stage 12 Temperature Setting Value 25.0℃ or 77.
For example, setting TS=25.0°C, CD=2.0°C, HD=3.0°C, when the measured temperature value ≤ 22°C (TS-HD), the controller will enter the heating state; when the measured temperature value ≥ 25°C, the heating will stop; when the measured temperature value ≥27.0°C(TS+CD),the controller enter the cooling state; when measured temperature value ≤ 25.0°C, cooling will stop; 4.1.1.
return to normal display and control. Or press any button to turn the buzzer alarm off only. 4.3 Compressor Delay Time(PT) In the cooling mode, when the power is turned on for the first time, PV(measured temperature value) ≥ TS(Temperature setting value) + CD(Cooling difference value), it will not start cooling immediately, but waiting for a delay time(PT).
completed, the detailed status is described in 6.4.6.8. 4.6.2 TR is the parameter for whether the timer function is enabled. 0 is off and 1 or 2 is on. 4.6.2.1 TR=0,Temperature Control Mode The timer function will not start, all the setting parameters after the parameter TR will not shows in the menu, and there is no need to set. 4.6.2.
27 28 29 30 31 32 33 34 35 36 37 38 39 35 35 35 3 3 3 34 35 35 35 35 35 35 35 35 35 35 35 35 3 3 3 3 3 3 3 3 3 3 3 3 The above table is the difference between the continuous timer mode and the target timer mode of the thermostat, which is represented by the curve image as follows: Temperature Timer mode CS Continuous vs.
stage will not enter the next time-temperature control until the current stage is completed. 4.6.8 U01~U12 are the parameters for the user to determine whether to alarm or not, setting to n=No Alarm; A= Alarm; C= Confirm; S=Stop Program. 4.6.8.1 UX=n: If the current stage is set to n, the next cycle control is entered; if the execution of the cycle index MD is completed, all output controls are turned off, PV shows the current temperature, and SV shows End. 4.6.8.
control will be entered in the next stage. If the execution of the cycle index MD is completed, PV shows the current temperature and SV shows End. 4.7 Manual or Automatic Mode ( AT ) AT is the power on operation mode after power off. AT=0:Manual Mode, after power off to re-power, the temperature controller will stop working, PV display flicker, buzzer will beep every one second, prompting the user to reset the parameters, after saving and exiting, the temperature controller restart the work.
Part 4 ITC-608T DUAL TEMPERATURE PROBES Controller Manual 26
1 Get to Know the Controller A WORK1 88.6 ff 98.
A Functions on screen PV:In normal mode, the P1 measured temperature is displayed. In settings mode, it will display menu code. P1 Cooling indicator LED 86.8 f 96.8 f P1 Heating indicator LED P1 Heating indicator LED: If P1 Temperature Control Function selected heating mode, the indicator LED is on, otherwise off. P1 Cooling indicator LED: If P1 Temperature Control Function selected cooling mode, the indicator LED is on, otherwise off. SV:In normal mode, the P2 measured temperature is displayed.
B Output(WORK1/WORK2) Instruction WORK1: The P1 heating/cooling output WORK2: The P2 heating/cooling output C Indicator LED: ●Red LED is on WORK1 output is on. ●Red LED is blinking WORK1 output is performing the function of compressor delay. ●Green LED is on WORK2 output is on. ●Green LED is blinking WORK2 output is performing the function of compressor delay. ●Yellow LED is on The controller is in the setting mode. D Button Instruction Please read the detail on 2.
2 Button Operation Instructions 2.1 Restore Default Data Press the “ " button to power on, the buzzer will make a short call, indicating that all parameters of both temperature probes function return to the default setting value. 2.2 Button Function in Normal Operation Mode Press “ ", PV shows temperature setting value of probe 1, it will be back to the normal display if there is no operation for 3 seconds or pressing the "SET" button.
3 Menu Instruction 3.1 Menu Setting Flow Chart Press "SET" Key for over 2 seconds to enter parameters setting mode STE Temperature Unit STE Y Heating or Cooling Mode Temperature Setting Value TS2 77.0℉ STE Alarm High Temperature Limit Alarm Low Temperature Limit Compressor Delay Time Heating or Cooling difference value DS2 3.0℉ CF F STE STE Alarm High Temperature Limit AH2 212℉ HC1 H STE STE Alarm Low Temperature Limit AL2 -40.0℉ TS1 77.
3.2 Dual Temperature Probes Setup Menu Description Code Menu Function Setting Range Default Setting CF Fahrenheit or Celsius Setting C or F F HC1 Heating or Cooling Setting TS1 Temperature Setting DS1 Setting Value for Heating or Cooling Difference H or C H -40.0℃~120℃ 25.0℃ -40.0℉~248℉ 77.0℉ 0.3℃~15.0℃ 2.0℃ 0.5℉~30.0℉ 3.0℉ -40.0℃~100℃ 100℃ AH1 High Temperature Alarm -40.0℉~212℉ 212℉ AL1 Low Temperature Alarm -40.0℃~100℃ -40.0℃ -40.0℉~212℉ -40.
WORK2 probe 2 output state indicator. 4.1 Control Function of Probe 1 When HC1=H, the temperature mode is heating mode, PV LED 1 is on, and when the measured temperature ≤ temperature setting value TS1 - difference value DS1, it enters the heating state, the WORK1 indicator is on, and the WORK1 relay works. When the measured temperature ≥ temperature setting value TS1, the WORK1 indicator is off and the WORK1 relay is off.
AL1, buzzer off and return to normal display and control. Or press any button to turn the buzzer alarm off only. 4.3.
5.3 Fahrenheit or Celsius Settings (CF) The users can set the display unit to Fahrenheit or Celsius according to their habits. The default temperature is Fahrenheit. If you need to display the unit in Celsius, then set the CF to C. Please note that when the CF changes state, all setting values are restored to the default setting and the buzzer gives a short beeping prompt.
Part 5 ITC-608T HUMIDITY Controller Manual Equivalent to IHC-200 Humidity Controller Manual 36
1 Get to Know the Controller A WORK1 WORK2 56.8 66.
A Functions on screen PV:In normal mode, the measured humidity is displayed. In settings mode, it will display menu code. SV:In normal mode, the humidity setting value is displayed. In setting mode, it will display the setting value. B Output(WORK1/WORK2) Instruction WORK1: The humidification output WORK2: The dehumidification output C Indicator LED: ●Red LED is on WORK1 output is on. ●Green LED is on WORK2 output is on.
2 Button Operation Instructions 2.1 Restore Default Settings Press " " button to power on, the buzzer will make a short call, indicating that all parameters of the user's humidity probe function return to the default setting value. 2.
3. Menu Instruction 3.1 Setting mode Flow Chart Press "SET" Key for over 2 seconds to enter parameters setting mode HS 50.0%RH SET Humidity Set Value HD 5.0%RH SET Humidification difference value DD 5.0%RH SET Dehumidification difference value AH 99.0%RH SET Alarm High humidity Limit AL SET 5.0%RH SET Alarm Low humidity Limit PT 0Minute Compressor Delay Time SET CA 0.
3.2 Setting Menu Instruction Code Symbol HS HS HD DD AH AH AL PT CA CA Function Humidity Setting Value Humidification Difference Value Dehumidification Difference Value Alarm High Humidity Limit Alarm Low Humidity Limit Compressor Delay Time Humidity Calibration Setting Range Default Setting 5.0%RH ~99.0%RH 50.0%RH 1.0%RH ~20.0%RH 5.0%RH 1.0%RH ~20.0%RH 5.0%RH 5.0%RH ~99.0%RH 99.0%RH 5.0%RH ~99.0%RH 5.0%RH 0~10 minutes 0 minute -20.0%RH ~20.0%RH 0.0%RH 4.
stop; When the measured humidity value is ≤ 42%RH (HS-HD), the controller will enter the humidification state , and when the measured humidity value is ≥ 50%RH, the humidification will stop. 4.2 Alarm High / Low Humidity Limit Settings (AH,AL) When measured humidity ≥ AH(alarm high humidity limit), PV shows alternate AH with measured humidity, buzzer will “bi-bi-Biii” alarm, until the humidity
Part 6 ITC-608T TEMPERATURE& HUMIDITY Controller Manual Equivalent to IHC-230 Temperature & Humidity Controller Manual 43
1 Get to Know the Controller A WORK1 88.6 f 56.
A Functions on screen PV:In normal mode, the measured temperature is displayed. In settings mode, it will display menu code. 86.8 56.8 Cooling indicator LED Heating indicator LED f Heating indicator LED: If Temperature Control Function selected heating mode, the indicator LED is on, otherwise off. Cooling indicator LED: If Temperature Control Function selected cooling mode, the indicator LED is on, otherwise off. SV:In normal mode, the measured humidity is displayed.
B Output(WORK1/WORK2) Instruction WORK1: The heating/cooling output WORK2: The humidification/dehumidification output C Indicator LED: ●Red LED is on WORK1 output is on. ●Red LED is blinking WORK1 output is performing the function of compressor delay. ●Green LED is on WORK2 output is on. ●Green LED is blinking WORK2 output is performing the function of compressor delay. ●Yellow LED is on The controller is in the setting mode. D Button Instruction Please read the detail on 2.
2 Button Operation Instructions 2.1 Restore Default Settings Press and hold the “ " button to power on, the buzzer will make a short call, indicating that all parameters of the user's temperature and humidity probe function return to the default setting value. 2.
3 Menu Instruction 3.1 Setting mode Flow Chart Press "SET" Key for over 2 seconds to enter parameters setting mode =T? Y HC H Heating or Cooling Mode N Humidificationi or Dehumidification Mode SET TS 77.0℉ Temperature Setting Value SET Humidity Setting Value HD H SET HS 50.0%RH SET DS Heating or Cooling difference value Humidificationi or Dehumidification difference value SET AH 99.0%RH Alarm High Humidity Limit SET AH Alarm High Temperature Limit SET Alarm Low Humidity Limit AL SET 5.
3.3.2When Code is T Symbol Function Setting Range Default Setting HC HC Heating or Cooling mode H or C H TS TS Temperature Setting Value -40.0℃~100℃ 25.0℃ -40.0℉~212℉ 77.0℉ DS s Heating or Cooling Difference Value 0.3℃~15.0℃ 2.0℃ 1.0℉~30.0℉ 3.0℉ AH AH Alarm High Temperature Limit -40.0℃~100℃ 100℃ -40.0℉~212℉ 212℉ AL AL Alarm Low Temperature Limit -40.0℃~100℃ -40.0℃ PT P Compressor Delay Time CA CA Temperature Calibration CF CF Fahrenheit or Celsius Settings -40.
4.2 Humidity Control Function (HD,HS,DS ) When HD=H, it is humidification mode, Humidification indicator LED is on . When PV(measured humidity) ≤ HS(humidity setting value) – DS(humidification or dehumidification difference setting value),green led is on, WORK2 output works; when PV(measured humidity) ≥ HS(humidity setting value),green led is off, and the WORK2 output is off. When HD=D, it is dehumidification mode, Dehumidification indicator LED is on.
a delay time(PT). When two adjacent of cooling starting intervals are greater than the delay time, it will immediately start cooling ; When two adjacent of cooling starting intervals are less than the delay time, it needs to operate the remaining delay time to start the cooling. Delay time will start counting from the WORK1 output off.
Inkbird Tech.C.L support@ink-bird.com www.ink-bird.