4.2 Humidity Control Function (HD,HS,DS )
When HD=H, it is humidification mode, Humidification 
indicator LED is on . When PV(measured humidity) ≤ 
HS(humidity setting value) – DS(humidification or dehumidifi-
cation difference setting value),green led is on, WORK2 output 
works; when PV(measured humidity) ≥ HS(humidity setting 
value),green led is off, and the WORK2 output is off.
When HD=D, it is dehumidification mode, Dehumidification 
indicator LED is on. When SV(measured humidity) ≥ 
HS(humidity setting value) + DS(humidification or dehumidifi-
cation difference setting value),green led is on, and the 
WORK2 output works; green led is blinking , indicating the 
dehumidification device is in the delay protection state; when 
SV(measured humidity) ≤ HS(humidity setting value), green 
led is off and the WORK2 output is off.
4.3 Alarm High / Low Temperature Limit Settings(AH,AL)
When measured temperature ≥ AH, high temperature limit 
alarm, PV shows alternate AH with current temperature , 
buzzer will “bi-bi-Biii” alarm, until the temperature <AH, buzzer 
off and return to normal display and control. Or press the 
button to turn the buzzer alarm off only.
When measured temperature ≤ AL, low temperature limit 
alarm, PV shows alternate AL with current temperature, buzzer 
will “bi-bi-Biii” alarm, until the temperature >AL, buzzer off and 
return to normal display and control. Or press the button to 
turn the buzzer alarm off only.
4.4 Alarm High / Low Humidity Limit Settings (AH,AL)
When measured humidity ≥ AH, high humidity limit alarm, SV 
shows alternate AH with current humidity, buzzer will 
“bi-bi-Biii” alarm, until the humidity <AH, buzzer off and return 
to normal display and control. Or press the button to turn the 
buzzer alarm off only.
When measured humidity ≤ AL, low humidity limit alarm, PV 
shows alternate AL with current humidity, buzzer will 
“bi-bi-Biii” alarm, until the humidity <AL, buzzer off and return 
to normal display and control. Or press the button to turn the 
buzzer alarm off only.
4.5 Cooling /Dehumidification Delay Protection Time(PT)
In cooling mode,when the power is turned on for the first 
time, it will not start the cooling immediately when PV(mea-
sured temperature value) ≥TS(temperature setting 
value)+DS(heating or cooling difference value),but waiting for 
 Output(WORK1/WORK2) Instruction
WORK1: The P1 heating/cooling output
WORK2: The P2 heating/cooling output
 Indicator LED:
●Red LED is on  WORK1 output is on.
●Red LED is blinking WORK1 output is performing the 
function of compressor delay.
●Green LED is on WORK2 output is on.
●Green LED is blinking WORK2 output is performing the 
function of compressor delay.
●Yellow LED is on The controller is in the setting mode.
 Button Instruction
Please read the detail on 2.Button Operation Instructions  below
Probe interface
Two temperature probes can be insert into P1 and P2 interface.
 Temperature probe
●If the controller display Er, you may get a false temperature 
probe, please try harder to insert the probe and rotate it to make 
good contact. If the problem is still persists, it is likely the 
internal probe wire has been damaged by the moisture or heat 
temperature. 
●The probe and cable cannot be touched by the flame. 
●Do not exceed the probe temperature range to avoid 
damaging.
2 Button Operation Instructions
2.1 Restore Default Settings
Press and hold the “ " button to power on, the buzzer will 
make a short call, indicating that all parameters of the user's 
temperature and humidity probe function return to the default 
setting value.
2.2 “ ” and “ ”Button Function in Normal Operation 
Mode
Press the “ ", PV shows the current temperature setting 
value , SV shows current humidification value; press “ ", PV 
shows current temperature value, SV the current humidification 
setting value , and It will be back to the normal display if there is 
no operation for 3 seconds orpressing the "
SET" button. 
2.3 “SET” Button Function in Normal Operation Mode 
Short press the “
SET” button to enter the quick setting 
temperature and humidity value mode. PV shows the current 
temperature setting value and flashes, and short press “ ” or 
“ ” button to increase or decrease the setting value, long 
press “ ” or “ ”button to quickly increase or decrease the 
setting value, Short press the “
SET” button again,SV shows 
the current humidity setting value and flashes, and short press 
“ ” or “ ” button to increase or decrease the setting value, 
long press “ ” or “ ”button to quickly increase or decrease 
the setting value and lastly press the "
SET" button again to 
confirm and exit. If there is no operation, it will automatically 
exit after 10 seconds and save the setting value.
2.4 Button Function in Setting Mode
When the controller is working normally, press the “SET” button 
for 2 seconds to enter the setting mode,the PV shows the first 
menu code“
 ”, SV shows the corresponding setting value. 
Press “
SET” button to scroll down the menu item and save the 
parameters of the previous menu item. Press“ ” or 
“ ”button to change the current setting value. Selected T to 
enter the temperature parameter modification mode; selected H 
to enter the humidity parameter modification mode. If in the 
setting state, there is no operation within 30 seconds or long 
press "
SET" button for 2 seconds, it will exit and save the 
setting state and return to normal operation mode.