User Manual
ITC-1000 User Manual
Inkbird Tech. Co., Ltd. www.ink-bird.com
8
6. Menu Instruction
6.1 When the set temperature is degrees Celsius (FCC)
Code
Function
Set range
Default
Note
TS
Temperature Set Value
-50~99.9
o
C
10.0
o
C
DS
Difference Set Value
0.3~15
o
C
1.0
o
C
PT
Compressor Delay
0~10 minutes
3munites
CA
Temperature Calibration Value
-15
o
C~15
o
C
0
o
C
CF
Fahrenheit or Celsius Setting
C
6.2 When the set temperature is degrees Fahrenheit (FCF)
Code
Function
Set range
Default
Note
TS
Temperature Set Value
-50~210
o
F
50
o
F
Min. Unit 1
o
F
DS
Difference Set Value
1~30
o
F
3
o
F
PT
Compressor Delay
0~10 minutes
3 minutes
CA
Temperature Calibration Value
-15~15
o
F
0
o
F
CF
Fahrenheit or Celsius Setting
F
Note:
When CF value change, all the set values restore to default value.