1. Safety Precautions 
  Ensure the product using within the specification.           
  Do  not  touch  the  terminals  at  least  while  power  is  being  supplied.  Doing  so  may 
occasionally result in injury due to electric shock. 
  Do  not  allow  pieces  of  metal,  wire  clippings,  or  fine  metallic  shaving  or  filings  from 
installation  to  enter  the  product.  Doing  so  may  occasionally  result  in  electric  shock, 
fire, or malfunction.   
  Do  not  use  the  product  where  subject  to  flammable  or  explosive  gas.  Otherwise, 
injury from explosion may occasionally occur.         
  Never  disassemble,  modify  or  repair  the  product  or  touch  any  of  the  internal  parts. 
Electric Shock, fire, or malfunction may occasionally occur.       
  If the output relays are used past their life expectancy, contact fusing or burning may 
occasionally  occur.  Always  consider  the  application  conditions  and  use  the  output 
relays  within  their  rated  load  and  electrical  life  expectancy.  The  life  expectancy  of 
output relays varies considerably with the output load and switch conditions. 
2. Specification 
Mounting dimension 
  Front Panel Dimension: DIN (48WmmX48Lmm) 
  Cutout size: 45x45mm 
Main Features 
  Support  Multiple  Thermocouples  and  Resistance  Sensors  (K,  S,  Wre,  T,  E,  J,  B,  N, 
CU50, PT100) 
  Wide Controlling Range: -50~1300ºC (K sensor) 
  High  Accuracy  of  Displaying  and  Controlling  0.1ºC,  Accuracy  of  Measurement 
±0.2%FS 
  PID and ON/OFF Control Mode, High Standard Self-adjusting Function 
  Multiple Outputs and Alarm Modes 
  Build-in Adjustable Digital Filter Reduce Interference 
  The Self-adjusting Function and Intelligent Control of the Instrument Ensure the Long-
term Stability 
  High Luminance, 0.39” height LED display, Anti-glare panel 
  Built-in Switch Power Supply, Wide Voltage Range and Low-power Consumption 