Installation guide

Themicrowave hoed isset for ventless(recirculating)
installation. For wall or roof ventingchanges to the
venting system mast be made.
CAUTION: To reduce risk of fire and to
proper_y exhaust air, be sure to vent air
outside. Do not vent exhaust air into
spaces within walls or ceilings or into
attics, craw_ spaces or garages.
For wall or roof ventingmethods:
Choosebetween roof venting or wali venting.
If the wail exhaust method is chosen, be surethat there is
proper clearancewithin the wall for the exhaust vent.
Vent materiamsneeded for installationare not incmaded.
Wall and roof caps mast have back-draft damper.
We recommend:
7. using rigid metal vent,
7. that length of vent and number of elbows should be
kept to a minimum to provide efficient performance,
7. that size of vent should be uniform,
7. using duct tape to seal all joints in the vent system,
7. using caulking compound to seal exterior waft or roof
opening around cap,
7. two elbows should not be installed together,
We do NOTrecommend:
7. flexible metal vent,
NOTE:If flexibie metai vent must be used,caicuiateeach
foot of fiexibte metal vent as two feet of rigid motetvent.
Flexible metalelbows count twice as much as standard
elbows.
Vertical venting
Saiida de aire per ei cieio rose
root cap
eaperoza de sielo race
3-1/4" x 1g" through4he-roof
a tray,s del sielo race per ue erifisio
de 3-1/4" x 18
Wail venting
Saiida de aire per ia pared we,sap
,,,_,_._ saperoza de pared
".£ 3-1/4" x lg" through-the-wall
o tray,s de la pared per oe
orifisio de 3=1/4"x 10
Ronnd vent transition
Transicibn de condncto de saiida de aire redondo
3" raieimem height (required for
damper to folly open)
Altura mieima de 3" (eeseearia
para qua la sompoerta se abra
sompletameefe)
\
3-1/4" x 18""to b""raced vent
traeeitioe
traneisibe de soeduste de salida
de dire redendo de 34/4" x 10"
ab"
Salida de dire
La campana damhomo ha side dise_ada pare set instamada
sin salida de dire (recircalacidn), Pard salida de dire en la
pared a en el cielo raso, dehen hacerse camhios en em
sistema de salida de aire.
PRECAUCION: para reducir el riesgo de
incendio y para instaiar el sistema de
salida de aire adecuado, asegQrese de
que el aire salga al exterior. No ponga la
salida de aire en espacios dentro de
paredes o cielos rases o en _ticos,
sbtanos de peque_a altura o garajes.
Pare m_tedos de salida de aire a travds de la pared e el
cielo rasa:
Decidaentre instalar la satida de airea travbs det cieto raso o
de una pared.
Si se decide per et mbtodo de salida de aire a travbs de ia
pared, aseg_resede que hayae! espacio adecuadodentro de
la paredpare et conducto de saiida de aire.
No se inclayenlea materiaies del candacto de salida de aire
qae se necesitan pare la instalacidn.
Lascaperuzas pard ciemaraso y pared dehen tenor
cempaerta de centratiro.
Recomendamos:
7" user un conducto de salida de aire metAticoy rigido.
7' que ia iongitud de! conducto de saiida deaire y ei n_mero
de codes se mantengana un minima para Iograr un
rendimiento eficiente.
7" qua ias dimensiones dei conducto sean uniformes.
7' user cinta para conducto paraseiiar todas ias uniones en el
sistema de saiida de aire.
7' usar masiiia pare caiafatearpara seiiar ia paredexterior ola
abertura en e! cielo raso alrededor de ia caperuza.
7' no se @ben instalar dos codes juntos.
NO recomeedamos:
7" conducto de salida deaire met_Iico flexible
NOTA:si debe usarse un conducto met_iico fiexibie, caicule
cada pie de conducto met_iico flexibie come si fueran dos pies
de conducto met_Iico rigido. Los codes de metal flexible hacen
per dos codes est_ndar.
6
Recommended ventlength:
Use 3=1/4"X 10" rectangular or 6" round vent.
The totai iength of the vent system inciuding straight vent,
elbow, transitions, waft or roof caps must not exceedthe
equivaient of 140 feet of 3=1/4'' X 10" rectangular or 6"
diameter round vent.
For best performance, use no more than three 90 degree
elbows.
To caicuiate the iength of system you need, add the
equivalentfeet for each vent piece used in the system=See
the following examples:
3-1/4" x 10" vent system:
1 =3=1/4"x 10"
90°eibow = 25 ft.
I =waii cap = 40 ft.
8 feet straight = 8 ft.
Length of
3-1/4" x 10" system = 73 ft.
5" vent system:
I =transition = 5 ft.
2 =90° elbows = 20 ft.
I =waii cap = 40 ft.
8 feet straight = 8 ft.
Length of 6" system = 73 ft.
If the existing vent is round, a rectangular=to=roundadapter
must be used and a rectangular 3" extension vent between
the damper assemblyand adapter must be instaibd to
prevent damper from sticking.
Recommended standard fittings
Accesorios estdndar recemendados
3-1/4"x lO"to 6"=5ft,
De3-1/4"x lO"a 6"=
5 pies
3q/4" x 10"roofcap=24ft,
Caperuzade cielorasode
3-1/4"x10"= 24pies
3-1/4"x 10"waltca
90:_elbow=10ft, =40fL
Codede90:)= Capemzade pared
10 pies de3-1/4"x 10"=
40 pies
3-1/4"x 10"
90 elbow=25ft,
Codede90 y 3q/4" x
10"=25 pies
iiiiii iili!'
::::::::::i:_iiiiiiiiiiii........ e£iiiiil;!:i}}_
3-1/4"x 10"ftat
elbow= 10 ft.
8odepianode3-1/4"
10"= 10pies
3-1/4"x 10" vent system
Sistema de salida de aire de 3-1/4" x 18"
3=1/4"x 10"
gO° elbow
Cede de 9g° y b ft.
3=1/4"x 10'' _ 6 pies _____a_I
wall sap
saperuza de
pared
6" ventsystem
Sistema de saiida de aire de 6"
gO° elbows
code de gg°
T
2 ft. (2 pies)
Langitudrecomendada dot cendacte de salida de aire:
Use un conducto de salida de aire rectanguiar de 3-1/4" x 10"
o redondo de 6".
La iongitud totai del sistema de saiida de aire, inciuyendo ei
conducto desaiida de aire recto, et code, Instransiciones, las
caperuzasde paredo cielo raso no @ben exceder e!
equivaientea 140 pies de conducto rectangular de saiida de
aire de 3-1/4" x 10"o conducto redondo de 6" de di_metro.
Para mejores resuitados, no use mAsde tres codes de 90°.
Parecaicular ia iongitud dei sistema qua necesita,agregue ia
equivatenciaen pies para cada pedazo de conducto usa@ en
et sistema. Vealos siguientes ejempios:
Siste_a de saiida de aire de 3-1/4" x 18":
1 =Code de 90°
y 3=1/4"x 10" = 25 pies
1 =Caperuzade pared = 40 pies
8 pies recto = 8 pies
Longitud de un
sistema de 3-1/4" x 10" = 73 pies
Siste_a de saiida de aire de 5":
I =transiciOn = 5 pies
2 =codes de 90° = 20 pies
I =caperuzade pared = 40 pies
8 pies recto = 8 pies
Longitud de un
sistema de 6" = 73 pies
Si ei actual conducto de salida de aire es redondo, debe usarse
un adaptador de rectanguiar a redondoyun conducto de
extensi6n rectangular de 3" entre el conjunto de ia compuerta
y se debeinstatar el adaptador pareevitar qua la compuerta se
atasque.
troesition
treeeisibn 7