Reference Manual
10
Control Options
Solid State Relay Panel
n
Infratech’s Solid State Panels are UL/CUL Listed
and are engineered for your individual project and
suitable for commercial or residential installations
of any size.
n
The Solid State Relay Panel will be fed from the
facility’s main panel at 125% (includes safety
factor) of the full amperage of all heaters.
n
There is a maximum of 9000 watts at 240V (max.
of 8000 watts at 208V per each Relay in the Panel
(50 amps max).
n
5,000 watt and 6,000 watt heaters must be on
their own relay.
n
Multiple heaters on a single relay are required to
be the same wattage.
n
Solid State Relay Panels can be built to accept
Single Phase or Three Phase power.
n
Solid State Relay Panels are designed project
specific, tested before leaving the factory, and
assigned a UL/CUL Listed Job Number.
n
Electrical wiring diagrams are provided for each
installation.
For use in conjunction with Zone Analog Controllers