Reference Manual

MINIMUM
2" X 8"
FRAMING
SUBFLOOR
5/8" DRYWALL WITH
1 HOUR FIRE RATING
2 X 8 STUDS MINIMUM
MINIMUM OPENINGS
43" FOR 39” HEATERS | 65.25" FOR 61" HEATERS
5/8" DRYWALL WITH 1-HOUR FIRE RATING (LINE ALL 5 SIDES OF CAVITY)
11.75"
4 FOOT FIXTURE WHIP WITH HIGH TEMP
CONNECTORS PROVIDED (CUSTOM LENGTH
WHIPS ALSO AVAILABLE), CONNECTION
MADE AT HEATER JUNCTION BOX.
JUNCTION BOX MUST BE MOUNTED
OUTSIDE OF THE LINED POCKET (TOP OR
SIDE). SEAL ALL PENETRATIONS AND SEAMS.
SIDE VIEW
47" FOR 39” HEATERS | 70.25" FOR 60" HEATERS
ADJUSTABLE TABS
3.75"
4"
SURFACE VIEW
MINIMUM
2" X 8"
FRAMING
SUBFLOOR
5/8" DRYWALL WITH
1-HOUR FIRE RATING
2 X 8 STUDS MINIMUM
MINIMUM OPENINGS
37" FOR 33" HEATERS | 43" FOR 39" HEATERS | 65.25" FOR 61" HEATERS
5/8" DRYWALL WITH 1-HOUR FIRE RATING MUST LINE ALL 5 SIDES OF CAVITY
11.75"
FIXTURE WHIP WITH
HIGH TEMP CONNECTORS
PROVIDED, CONNECTION
AT HEATER JUNCTION BOX.
JUNCTION BOX MUST
BE MOUNTED OUTSIDE
OF THE LINED POCKET
(TOP OR SIDE)
SIDE VIEW
47" FOR 39” HEATERS | 70.25" FOR 60" HEATERS
ADJUSTABLE TABS
3.75"
4"
SURFACE VIEW
Proper Flush Mount Installation
4
Mounting Options
Flush mount your heater in four simple steps
Frame the pocket that will house the heater with a
one hour-rated fire containment box. Note: Frame and
heaters cannot be mounted on a sloped/pitched ceiling.
The junction box must be mounted outside of the lined
pocket. You can choose to mount the junction box in
a variety of locations, depending upon where you’ll be
accessing it.
Install the frame into the finished pocket. You may
choose to leave all four inches of the trim exposed,
or partially cover it with a decorative ceiling
(1/2" clearance is required from ventilation holes).
Install the heater (heater must face horizontal to the
floor) and adjust the tabs to set the heater flush with
finished ceiling.
STEP
1
STEP
3
STEP
2
STEP
4
For video instructions of proper flush mount installation, visit www.infratech-usa.com or scan.
WARNING: FRAME AND HEATERS CANNOT BE FLUSH MOUNTED ON A SLOPED/PITCHED CEILING. FLUSH MOUNT
APPLICATIONS MUST ALWAYS BE INSTALLED WITH HEATERS HORIZONTAL TO THE FLOOR ON A FLAT, NON-SLOPED CEILING.
MINIMUM
2" X 8"
FRAMING
SUBFLOOR
5/8" DRYWALL WITH
1 HOUR FIRE RATING
2 X 8 STUDS MINIMUM
MINIMUM OPENINGS
37" FOR 33" HEATERS | 43" FOR 39" HEATERS | 65.25" FOR 61" HEATERS
5/8" DRYWALL WITH 1-HOUR FIRE RATING (LINE ALL 5 SIDES OF CAVITY)
11.75"
FIXTURE WHIP W/ HIGH
TEMP CONNECTORS
(PROVIDED) CONNECTION
MADE AT JUNCTION BOX
JUNCTION BOX MUST
BE MOUNTED OUTSIDE
OF THE LINED POCKET
(TOP OR SIDE)
SIDE VIEW
41" FOR 33" HEATERS | 47" FOR 39" HEATERS | 70" FOR 61" HEATERS
3.75"
4"
SURFACE VIEW
MINIMUM
2" X 8"
FRAMING
SUBFLOOR
5/8" DRYWALL WITH
1 HOUR FIRE RATING
2 X 8 STUDS MINIMUM
MINIMUM OPENINGS
43" FOR 39” HEATERS | 65.25" FOR 61" HEATERS
5/8" DRYWALL WITH 1-HOUR FIRE RATING (LINE ALL 5 SIDES OF CAVITY)
11.75"
FIXTURE WHIP W/ HIGH
TEMP CONNECTORS
(PROVIDED) CONNECTION
MADE AT JUNCTION BOX
JUNCTION BOX MUST
BE MOUNTED OUTSIDE
OF THE LINED POCKET
(TOP OR SIDE)
ADJUSTABLE TABS
3.75"
4"