User's Manual
Technical Document
430721-01
Rev. E
Indyme Solutions, Inc. 8295 Aero Place San Diego, CA 92123 USA +1.858.268.0717 +1.800.829.6141 Page 4 of 7
Press the SET button <1–4> times to select the input you are programming, RESET once to save. The
assurance led will flash to confirm your entry.
Press the SET button <1–4> times to select the Operating Mode, RESET once to save.
The assurance LED will flash to confirm your input number, pause, then flash to confirm your Operating
Mode entry.
NOTE: Operating Modes <5--6> are NOT valid for Individual Input Mode.
When Operating Modes <5--6> are set globally, Individual Input Mode is disabled.
Operating Modes
Mode-1: Alarm Notify Non-Latching
Basic alarm notification; compatible with “Shopper Help button” alarm processing.
When any INPUT is activated, an alarm SET is broadcast and the corresponding LED will flash according to “LED
Sequence 1”. (Indicated below.)
When the INPUT is deactivated, an alarm RESET is broadcast and the corresponding LED will turn off.
Mode-2: Alarm Notify Latching
Basic alarm notification, response required;
When any INPUT is activated, an alarm SET is broadcast and the corresponding LED will flash according to “LED
Sequence 1”. (Indicated below.)
When the INPUT is deactivated, NO alarm RESET is broadcast. The corresponding LED will continue to flash until
the front panel button is pressed.
Responding user must press the front panel button corresponding to the active INPUT to broadcast an alarm
RESET and turn off the LED. If a front panel button is pressed when the INPUT is not active, (non-alarm), an
alarm RESET is broadcast.
Mode-3: Alarm Reminder Non-Latching
Same as Mode 1 except, the alarm is re-started if the INPUT is not cleared. Periodically re-starts the alarm
sequence for situations in which a persisting alarm condition may be overlooked (such as an alarm sequence
that starts during unstaffed hours and does not self-clear). If alarm state persists more than XXX minutes (XXX
specified by CU-based variable in the range of 15 to 999 minutes; default is 30 minutes), then repeatedly re-start
this sequence from the beginning as a new alarm.
Mode-4: Alarm Reminder Latching
Same as Mode 2 except, the alarm is re-started if the corresponding front panel button is not pressed.
Periodically re-starts the alarm sequence for situations in which a persisting alarm condition may be overlooked
(such as an alarm sequence that starts during unstaffed hours and does not self-clear). If alarm state persists
more than XXX minutes (XXX specified by CU-based variable in the range of 15 to 999 minutes; default is 30
minutes), then repeatedly re-start this sequence from the beginning as a new alarm.
Mode-5: Director Buttons Latching
Four Button Director Help button; the four external inputs are disabled.
When user presses any of buttons 1 through 4, an alarm SET is broadcast and the corresponding LED will flash
according to “LED Sequence 1”. (Indicated below.) Responding user presses the front panel button “A”
(RESPOND) to clear all active alarm(s); an alarm RESET is broadcast and the corresponding LED(s) will turn off. If