Owner manual
800-446-7488 4 www.in-situ.com
10. Close the front panel and tighten the four front panel screws.
11. Apply power to the Con TROLL PRO.
12. Program the relay outputs to match the selected configuration.
Configuring a Single-Parameter Light Alarm
In this scenario, the Con TROLL PRO monitors a tank using an RDO
®
PRO Probe. The
Con TROLL PRO turns on an aerator when the dissolved oxygen (DO) concentration
falls below 4 mg/L. The light tower shows green when the DO is above 4 mg/L (aerator
off), and yellow when the DO is below 4 mg/L (aerator on).
The RDO PRO Probe is wired as Probe A. Relay 1 is used to implement the control
and display function.