User Manual
 Card Setup 
Sealevel Systems ULTRA COMM+422.PCI Page 5 
Line Termination 
Typically, each end of the RS-485 bus must have line terminating resistors 
(RS-422 terminates the receive end only). A 120-ohm resistor is across each 
RS-530/422/485 input in addition to a 1K ohm pull-up/pull-down combination 
that biases the receiver inputs. Headers J1A – J4A allow the user to customize 
this interface to their specific requirements. Each jumper position corresponds to 
a specific portion of the interface. If multiple ULTRA COMM+422.PCI 
adapters are configured in an RS-485 network, only the boards on each end 
should have jumpers T, P & P ON.  Refer to the following table for each 
position’s operation: 
Name Function 
P  Adds or removes the 1K ohm pull-down resistor in the 
RS-422/RS-485 receiver circuit (Receive data only). 
P  Adds or removes the 1K ohm pull-up resistor in the 
RS-422/RS-485 receiver circuit (Receive data only). 
T  Adds or removes the 120 ohm termination. 
L  Connects the TX+ to RX+ for RS-485 two wire operation. 
L  Connects the TX- to RX- for RS-485 two wire operation. 
P P T L L
Figure 6 - Headers J1A – J4A, Line Termination 