Instruction Manual
  Card Setup 
Sealevel Systems COMM+2/EX Page 2 
Card Setup 
The COMM+2/EX contains several jumper straps which must be set for proper operation. 
Address Selection 
Each port on the COMM+2/EX  occupies eight consecutive I/O locations. A DIP-switch is used to set the base 
address for these locations. Be careful when selecting the base address as some selections conflict with existing 
ports. The following table shows several examples that typically do not cause a conflict. SW1 sets the I/O address for 
port 1 of the COMM+2/EX and SW2 sets the address for port 2. 
Address  Binary  Switch Position Setting 
Hex  A9  A0  1 2 3 4 5  6  7 
280-287 1010000XXX Off On Off On On On On 
2A0-2A7 1010100XXX  Off On Off On Off  On  On 
2E8-2EF 1011101XXX Off On Off Off Off On  Off 
2F8-2FF 1011111XXX Off On Off Off Off Off Off 
3E8-3EF  1111101XXX  Off Off Off Off Off  On  Off 
300-307 1100000XXX Off Off On On On On On 
328-32F 1100101XXX Off Off On On Off On Off 
3F8-3FF 1111111XXX Off Off Off Off Off Off Off 
Figure 1 - Address Selection Table 
The following illustration shows the correlation between the DIP-switch setting and the address bits used to 
determine the base address. In the example below, address 300 is selected as a base. Address 300 in binary is XX11 
0000 0XXX where X = a non-selectable address bit. 
ON
12345 6 78
ENA3A9
Figure 2 - DIP-Switch Illustration 
Note: Setting the switch ‘On’ or ‘Closed’ corresponds to a ‘0’ in the address, while leaving it ‘Off’ or ‘Open’ 
corresponds to a ‘1’. 
Refer to Appendix A for common address contentions. 










